  • Page 2 ___________________ Digital input module Preface DI 16x24VDC ST ___________________ Documentation guide (6ES7131-6BH00-0BA0) ___________________ SIMATIC Product overview ___________________ Connecting ET 200SP Digital input module ___________________ DI 16x24VDC ST Parameters/address space (6ES7131-6BH00-0BA0) ___________________ Interrupts/diagnostic alarms Manual ___________________ Technical specifications ___________________ Parameter data record...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 5: Table Of Contents

    Interrupts ..........................20 Diagnostic messages ......................20 Technical specifications ........................21 Technical specifications ......................21 Parameter data record .......................... 24 Parameter assignment and structure of parameter data record ..........24 Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 6: Documentation Guide

    You can download the documentation free of charge from the Internet (http://w3.siemens.com/mcms/industrial-automation-systems-simatic/en/manual- overview/tech-doc-et200/Pages/Default.aspx). Changes and supplements to the manuals are documented in a Product Information. You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/73021864). Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 7 You need to register once to use the full functionality of "mySupport". You can find "mySupport" in the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area of "mySupport", you have the possibility to combine complete manuals or parts of them to make your own manual.
  • Page 8 With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool). Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 9: Product Overview

    Color code for selecting the color identification labels ⑤ ⑪ LEDs for channel status Article number ⑥ LED for supply voltage Image 2-1 View of the module DI 16×24VDC ST Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 10 ● Color identification labels ● Reference identification label ● Shield connector See also You can find additional information on the accessories in the system manual ET 200SP distributed I/O system (https://support.industry.siemens.com/cs/ww/en/view/91696622). Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 11: Connecting

    Connecting Wiring and block diagram This section includes the block diagram of the DI 16x24VDC ST module with the terminal assignments for a 1-wire connection. Information on wiring the BaseUnit can be found in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293).
  • Page 12 3.1 Wiring and block diagram Wiring: 1-wire connection The following figure shows the block diagram and an example of the terminal assignment of the digital input module DI 16x24VDC ST on the BaseUnit BU type A0 without AUX terminals (1-wire connection). ①...
  • Page 13: Parameters/Address Space

    Disable Module Module Disable • No supply voltage L+ Enable • Diagnostics Disable Module Module Disable • wire break Enable • Channel activated Enable Channel Channel Disable • Enable • Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 14 If required, you can assign these parameters using data rec- ord 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the I/O module is 4 bytes. Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 15: Declaration Of Parameters

    A potential group ends with the dark-colored BaseUnit, which follows a light-colored BaseUnit or server module in the station configuration. See also You can find additional information in the system manual ET 200SP distributed I/O system (https://support.industry.siemens.com/cs/ww/en/view/91696622). Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 16: Address Space

    1 x 16-channel without value DI 16x24VDC ST V1.1 status 1 x 16-channel with value status DI 16x24VDC ST V1.1, QI Evaluating the value status An additional two bytes are allocated in the input address space if you enable the value status for the digital module.
  • Page 17 (Quality Information (QI)). The addresses for the value status are only available if the value status is enabled. Image 4-1 Address space of the DI 16×24VDC ST with value status Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 18: Interrupts/Diagnostic Alarms

    Interrupts/diagnostic alarms Status and error display LED display The following figure shows you the LED display of the DI 16x24VDC ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Image 5-1 LED display Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0)
  • Page 19 Process signal = 0 Off
 Process signal = 1 PWR LED Table 5- 3 Status display of the PWR LED PWR LED Meaning Missing supply voltage L+ Off
 Supply voltage L+ present Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 20: Interrupts

    Firmware update is currently in progress Wait for firmware update. • unavailable or has been canceled. The module does Restart the firmware update. • not read in process values in this state. Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 21: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the DI 16×24VDC ST 6ES7131-6BH00-0BA0 General information Product type designation ET 200SP, DI 16x24VDC ST, PU 1 Firmware version V1.1 FW update possible • Usable BaseUnits BU type A0 Color code for module-specific color identification...
  • Page 22 With "1" to "0", min. • 20 ms With "1" to "0", max. • For interrupt inputs Configurable • for counters/technological functions Configurable • Cable length Shielded, max. 1000 m Unshielded, max. 600 m Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 23 75 V DC / 60 V AC (basic insulation) Insulation Insulation tested with 707 V DC (type test) Dimensions Width 15 mm Weights Weight, approx. 28 g Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/59753521) Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 24: Parameter Data Record

    The STATUS output parameter contains a corresponding error code. You will find a description of the "WRREC" instruction and the error codes in the STEP 7 online help. Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 25 Channel 0 includes the diagnostics enable for the entire module. Image A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Image A-2 Header information Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 26 The figure below shows the structure of the parameters for channels 0 to 15. You enable a parameter by setting the corresponding bit to "1". Image A-3 Structure byte x to x+1 for the channels 0 to 15 Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...
  • Page 27 • the WREC instruction. Wrong version or error in the header Correct the version, length and number of pa- information rameter blocks. Parameter error Check the parameters of the module Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0) Manual, 12/2015, A5E03573442-AD...