Siemens DI 16x24VDC ST Manual page 27

Simatic et 200sp digital input module
Hide thumbs Also See for DI 16x24VDC ST:
Table of Contents

Advertisement

Error transmitting the data record
The module always checks all values of the data record to be sent. The module applies the
values from the data record only when all values have been transmitted without errors.
The WRREC instruction for writing data records returns the appropriate error code if there
are errors in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Error code in the STATUS pa-
rameter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E1
Digital input module DI 16x24VDC ST (6ES7131-6BH00-0BA0)
Manual, 12/2015, A5E03573442-AD
A.1 Parameter assignment and structure of parameter data record
Meaning
xx
Number of the data record unknown
xx
Length of the data record incorrect
xx
Slot invalid or unavailable
xx
Wrong version or error in the header
information
xx
Parameter error
Parameter data record
Solution
Enter valid number for data record.
Enter valid value for data record length.
Check the station to determine whether the
module is plugged in or pulled.
Check assigned values for the parameters of
the WREC instruction.
Correct the version, length and number of pa-
rameter blocks.
Check the parameters of the module
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents