Summary of Contents for Siemens SIMATIC ET 200SP HA F-DI 16xNAMUR HA
Page 1
Cybersecurity information Preface Product overview SIMATIC Terminal ET 200SP HA F-DI 16xNAMUR HA Parameters/address space Applications of the F-I/O module Equipment Manual Displays, alarms and messages Technical specifications Response times 6DL1136-6TH00-0PH1 10/2024 A5E53588991-AA...
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
Page 6
Cybersecurity information F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
It supplements the system manual "Distributed I/O System ET 200SP HA (https:// support.industry.siemens.com/cs/de/en/view/109817158)". Functions that generally relate to the system are described in the system manual. The information in this device manual and the system/function manuals enables you to put the ET 200SP HA into operation.
Page 8
• SIMATIC Industrial Software • S7 F/FH Systems • Process control system, e.g. SIMATIC PCS 7 • ET 200SP HA You can find more information on setting up notifications on the page "Helpful Functions in Online Support (https://support.industry.siemens.com/cs/ww/en/sc/2063)". F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Product overview F-DI 16xNAMUR HA I/O module Definition The I/O module has the following properties: • Technical properties – 16 fail-safe digital inputs (SIL3/Cat.4/PLe) – 16 outputs for sensor supply – PROFIsafe Profile V2.6.1 – Module-specific diagnostics for missing supply voltage L+ –...
Page 10
Product overview 3.1 F-DI 16xNAMUR HA I/O module WARNING Validity of safety parameters The safety parameters in the technical specifications are valid for a mission time of 20 years and a repair time of 100 hours. If a repair is not possible within 100 hours, remove the relevant module from the terminal block or switch off its supply voltage before 100 hours elapse.
Page 11
Product overview 3.1 F-DI 16xNAMUR HA I/O module Description ① ⑧ Function class LEDs for channel status/channel fault ② ⑨ Color code Connection diagram • Basic type: "White" = Digital input module • Supplemental type information: "Yellow" = Fail-safe I/O module ③...
• Labeling strips • Color-coded labels • Reference identification label • Slot cover • Shield connector • Terminal blocks You can find additional information in the system manual "Distributed I/O System ET 200SP HA (https://support.industry.siemens.com/cs/de/en/view/109817158)". F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Product overview 3.3 Firmware update Firmware update Definition New firmware versions are provided by Siemens as needed for the F-I/O module F-DI 16xNAMUR HA and may contain function extensions and optimizations. A firmware update in RUN of the F-CPU is possible. Overview •...
Terminal Terminal blocks Definition The terminal blocks provide the process terminals (push-in terminals) for components such as devices to be connected. Terminal blocks You can operate the I/O module with the following terminal blocks: Article No. Color Description 6DL1193-6TP00-0DH1 Light gray For single operation (Push in) "New potential group"...
Page 16
Terminal 4.1 Terminal blocks Connections on the slot and I/O module Slot of the I/O module Plug side of the I/O module 1- 32 ① Carrier module contacts of the backplane bus: Maximum 50 mA Maximum 3.5 V DC ② Terminal block contacts of the I/O module: Maximum 30 V DC ...
Terminal 4.2 Terminal assignment Terminal assignment Definition The pin assignment provides information about the arrangement and terminal identification of the connections when wiring the terminal block. Description The pin assignment is as follows: Terminal Assignment Terminal Assignment Explanations F-DI /DI.0+ F-DI /DI.1+ F-DI /DI.n+: Input signal, channel n (0…15) F-DI /DI.2+ F-DI /DI.3+...
Terminal 4.3 Schematic circuit diagram Schematic circuit diagram Definition A block diagram is a schematic representation of the individual function blocks. Description The following figure shows the circuit diagram of the F-DI 16xNAMUR HA. Input connection Terminal 1 DI0 µC1 Galvanic isolation 16 DI15 MANA µC2...
Parameters/address space Configuration The following software is required to configure the I/O module: • S7 F Systems V6.4 SP1 (or higher) Parameters You define the functioning of the I/O module via parameters. F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Parameters/address space 5.1 Module/channel parameters Module/channel parameters Definition Module/channel parameters are specific parameters whose configuration can affect the entire module or channels. Introduction The parameters of the F-DI 16xNAMUR HA are described below. The parameters of the I/O module are displayed in the properties of the module. The "Time stamp"...
Page 21
Parameters/address space 5.1 Module/channel parameters Parameter Range of values Default value Parameter Scope reassign‐ ment in Sensor supply test (Page 27) Enabled All channels • Enabled • Disabled Sensor supply test - Test time (ms) 7 ms to 2 s (in 7 increments) 10 ms All channels (Page 28) Sensor supply test - Startup time of...
Page 22
ET200SP HA without time-stamp capability, and certain prerequisites are met. For more information on time stamping, refer to the "SIMATIC PCS 7 Process Control System High-Precision Time Stamping With Use of ET 200SP HA (https:// support.industry.siemens.com/cs/ww/en/view/109772337)" Function Manual. Parameter Range of values Default value Parameter re‐...
Parameters/address space 5.2 Description of the parameters Description of the parameters 5.2.1 F_source_address Definition Together, the F-source address "F_source_address" and the F-destination address "F_destination_address" form the PROFIsafe address. The PROFIsafe address is used for the unique identification of the F-I/O modules. The F-source address is a unique address of the F-CPU for the entire network.
Parameters/address space 5.2 Description of the parameters WARNING PROFIsafe addresses have to be unique across stations • Station-wide uniqueness: Fail-safe I/O modules of the ET 200SP HA are uniquely addressed station-wide by a combination of F-source address (PROFIsafe start address of the assigned F-CPU) and F- destination address.
Parameters/address space 5.2 Description of the parameters This parameter is "activated" by default, cannot be changed and is for display purposes only. 5.2.5 Behavior after channel fault Definition With this parameter you specify whether the entire F-module is passivated after channel faults or just the faulty channels: •...
Parameters/address space 5.2 Description of the parameters Pulse stretching for pulses with value "0" Process value Time "Pulse stretching (s)" Process value with pulse stretching Only pulses with value "0" are stretched. Pulses with value "1" are ignored Note If you configure pulse stretching for an input channel, it also affects flutter monitoring enabled for this channel.
Parameters/address space 5.2 Description of the parameters If no flutter error occurs over a period equal to three times the configured monitoring window, the diagnostic interrupt is reset. Principle of flutter monitoring: The following figure shows the principle of flutter monitoring. Parameter "Chatter monitoring - Number of signal changes"...
Parameters/address space 5.2 Description of the parameters The following short-circuits are detected: • Short-circuit of an input with a sensor supply of another channel • Short circuit on an input with the input of another channel • Short circuit of a sensor supply to sensor supply of another channel If the sensor supply test is disabled, you must route your cables in a short-circuit-proof and cross-circuit-proof manner.
Parameters/address space 5.2 Description of the parameters 5.2.12 Sensor supply test - Startup time of sensor after test (ms) Definition In addition to the switch-off time "Sensor supply test - Test time (ms)", a startup time must also be specified for performing the sensor supply test. You use this parameter to notify the module how long the utilized sensor needs to start up after the sensor supply is switched on again.
Parameters/address space 5.2 Description of the parameters A new potential group starts on the left side with a light gray terminal block, via which the supply voltage for the potential group is fed in. The potential group is continued to the right with dark gray terminal blocks and ends when a new potential group is built up to the right of it.
Parameters/address space 5.3 Address space Address space Abbreviations • "IB" stands for input byte, i.e. the module start address in the input area • "QB" stands for output byte, i.e. the module start address in the output area • "QDIn" stands for value status (QI) of digital input "n" "Value status"...
You can find more information on address assignment as well as evaluation and processing of the value status in the programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming (https://support.industry.siemens.com/cs/ww/en/view/ 109773062)". F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Applications of the F-I/O module Applications cases of the I/O module Definition In the following chapters, you will select applications for the F-I/O module and learn in each case how to wire the F-I/O module, which specific parameters you need to set, and which errors are detected.
Page 34
Applications of the F-I/O module 6.1 Applications cases of the I/O module Application Achievable SIL/ Sensor evaluation Sensor supply test Remark Cat./PL 3 / 4 / e 1oo2 Enabled equivalent Disabled You must implement the wiring in a short-circuit-proof and cross-circuit- (not on the module, on‐...
Applications of the F-I/O module 6.2 Application 1: Safety mode SIL3/Cat.3/PLd Application 1: Safety mode SIL3/Cat.3/PLd Definition Below is the wiring diagram and parameter assignment of the F-DI 16xNAMUR HA I/O module for application 1: • SIL3/Cat.3/PLd • 1oo1 evaluation Wiring You perform the wiring on the appropriate terminal block.
Applications of the F-I/O module 6.2 Application 1: Safety mode SIL3/Cat.3/PLd Parameter assignment Set the following parameters for the corresponding channel: Parameter Sensor type NAMUR sensor Pulse stretching (s) • None • 0.5 s • 1 s • 2 s Flutter monitoring - Number of signal changes •...
Applications of the F-I/O module 6.3 Application 2: Safety mode SIL3/Cat.4/PLe Application 2: Safety mode SIL3/Cat.4/PLe Definition Below is the wiring diagram and parameter assignment of the I/O module F-DI 16xNAMUR HA for application 2: • SIL3/Cat.4/PLe • 1oo2 evaluation • Application for two NAMUR sensors connected to two input channels of the same I/O module Wiring You perform the wiring on the appropriate terminal block.
Page 38
For safety-related applications according to SIL3/Cat.4/PLe, perform a discrepancy analysis with 1oo2 (2v2) evaluation in your safety program. You can find more information in the programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming (https:// support.industry.siemens.com/cs/ww/en/view/109802562/en)". F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Applications of the F-I/O module 6.4 Application 3: Safety mode SIL3/Cat.4/PLe Application 3: Safety mode SIL3/Cat.4/PLe Definition Below is the wiring diagram and parameter assignment of the F-DI 16xNAMUR HA I/O module for application 3: • SIL3/Cat.4/PLe • 1oo2 evaluation • Application for two NAMUR sensors connected to one input channel of two I/O modules Wiring You perform the wiring on the appropriate terminal block.
Page 40
Applications of the F-I/O module 6.4 Application 3: Safety mode SIL3/Cat.4/PLe WARNING Requirement for sensors To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor. (FDIW-007) Parameter assignment Set the following parameters for the corresponding channel: Parameter Sensor type NAMUR sensor Pulse stretching (s)
Page 41
For safety-related applications according to SIL3/Cat.4/PLe, perform a discrepancy analysis with 1oo2 (2v2) evaluation in your safety program. You can find more information in the programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming (https:// support.industry.siemens.com/cs/ww/en/view/109802562/en)". F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Applications of the F-I/O module 6.5 Requirements placed on sensors for fail-safe modules Requirements placed on sensors for fail-safe modules Definition There are certain requirements for the safety-related use of sensors, which are briefly described below. General sensor requirements For safety-related use of sensors, you must observe the following important warning: WARNING Sensor requirements Note that a significant responsibility for safety of instrumentation lies with the sensors.
Page 43
Applications of the F-I/O module 6.5 Requirements placed on sensors for fail-safe modules Requirements for the duration of the sensor signals WARNING Sensor signal requirements Observe the following requirements for the sensor signals: • To guarantee the correct acquisition of the sensor signals by F-modules with inputs, you must ensure that the sensor signals have a certain minimum duration.
Page 44
Applications of the F-I/O module 6.5 Requirements placed on sensors for fail-safe modules F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Displays, alarms and messages Status and error displays Definition The following figure shows the LED displays of the I/O module: F-DI 16xNAMUR HA DIAG MT 1 DI.0+ DI.1+ 3 DI.2+ DI.3+ 5 DI.4+ DI.5+ 7 DI.6+ DI.7+ DI.8+ DI.9+ DI.10+ DI.11+ DI.12+ DI.13+...
Displays, alarms and messages 7.2 LEDs LEDs 7.2.1 DIAG LED Definition The DIAG LED provides you diagnostic information. Description The diagnostic display of the DIAG LED is as follows: DIAG LED Meaning The supply voltage of the ET 200SP HA head module is disrupted or switched off.
Displays, alarms and messages 7.2 LEDs 7.2.3 Channel status / fault LEDs Definition The channel status and channel fault LEDs provide you information about the status and faults of the channels. Description The green "Channel status" LED indicates the signal level (1/0) only if an input is enabled. The red "channel fault"...
Displays, alarms and messages 7.2 LEDs Description The combination of the status and fault displays of the Channel status, DIAG and Channel fault LEDs is as follows: Channel sta‐ DIAG LED Channel fault Meaning tus LED • The PROFIsafe address is different from the config‐ ured PROFIsafe address.
Displays, alarms and messages 7.3 Interrupts Interrupts Definition Fail-safe digital input module F-DI 16xNAMUR HA supports diagnostic interrupts/messages and maintenance messages. Description The F-module generates a diagnostic interrupt for each diagnostic message described in section "Diagnostic messages (Page 51)". The following table provides an overview of the diagnostics interrupts of the F-module. The diagnostics interrupts are assigned either to one channel or to the entire F-module.
You can find more information on passivation and reintegration of F-I/O: • In the programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming (https://support.industry.siemens.com/cs/ww/en/view/ 109802562)" in section 8.2 "Positioning, interconnecting, and assigning parameters to F- Channel drivers".
Displays, alarms and messages 7.4 Diagnostic messages Diagnostic message Error Meaning Remedy code Error (000B) Voltage of internal voltage supply is too • Eliminate the electromagnetic inter‐ low. ference. Possible causes: • Replace the F-module. • Disruption of the internal voltage supply.
Displays, alarms and messages 7.4 Diagnostic messages Diagnostic message Error Meaning Remedy code Safety destination address not The F-module has detected an invalid F- Check the parameter assignment of the valid (F_Dest_Add) destination address. PROFIsafe driver. Safety source address not valid The F-module has detected an invalid F- (F_Source_Add) source address.
Displays, alarms and messages 7.4 Diagnostic messages Diagnostic message Error Meaning Remedy code Module is defective • Electromagnetic interference is • Eliminate the interference. The mod‐ higher than permitted. ule must then be pulled and plug‐ ged, or the power switched OFF and •...
Displays, alarms and messages 7.4 Diagnostic messages Diagnostic message Error Meaning Remedy code Short circuit or defective sensor A short-circuit of the sensor supply was • Eliminate the short circuit in the supply detected. process wiring. Possible causes: • Check the configured test time and •...
You can find additional information on diagnostics that pertains to all F-modules (e.g. readout of diagnostics functions, passivation of channels) in the programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming (https:// support.industry.siemens.com/cs/ww/en/view/109802562)". F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Displays, alarms and messages 7.5 Maintenance messages Maintenance messages Definition A maintenance event is generated every time a maintenance requirement is determined. The MT LED lights up on the module. Maintenance messages do not have a direct influence on the functions of the module or digital inputs.
Page 58
Displays, alarms and messages 7.5 Maintenance messages F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
For compliance with IEC 61131-2, EN 298, and NAMUR recommendation NE 21, use only power supply units (230 V AC --> 24 V DC) with a mains buffering time of at least 30 ms. You can find up-to-date information on the PS components on the Internet (http:// mall.automation.siemens.com). F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Page 60
Technical specifications Article number 6DL1136-6TH00-0PH1 General information Product type designation F-DI 16xNAMUR HA HW functional status Firmware version V1.0 • FW update possible Usable terminal block TB type H1, H0, P0 and N0 Color code for module-specific color identifica‐ CC01 tion plate Product function...
Page 61
Technical specifications Article number 6DL1136-6TH00-0PH1 Address area Address space per module 9 byte • Inputs 5 byte • Outputs Hardware configuration Automatic encoding • Mechanical coding element Digital inputs Number of digital inputs Digital inputs, parameterizable Pulse extension 0 / 0.5 / 1 / 2 s •...
Page 62
Technical specifications Article number 6DL1136-6TH00-0PH1 Yes; 100 ... 360 ohm • Short-circuit Diagnostics indication LED Yes; Yellow LED • MAINT LED Yes; green PWR LED • Monitoring of the supply voltage (PWR-LED) Yes; green LED • Channel status display Yes;...
Response times Response times Introduction The response times of F-DI 16xNAMUR HA digital input module are found below. The response times of the digital input module go into the calculation of the F-system response time. Definition of response time for fail-safe digital inputs The response time represents the interval between a signal change at the digital input and reliable availability of the safety frame on the backplane bus.
Page 64
Response times A.1 Response times The WCDT is the maximum of the channel-specific response times. WCDT = MAX (T [0..15]) RESP_CH OFDT (One Fault Delay Time) With short- and cross-circuit proof cable routing If the cable routing is designed to be short-circuit and cross-circuit proof, the following calculation regulation applies.
Page 65
Response times A.1 Response times For T >= 15000 ms: OFDT = T + 120 ms TEST_MAX : Corresponds to the time of the channel with the highest value for T TEST_MAX TEST. Example The following is configured for the channels 0 to 14: •...
Page 66
Response times A.1 Response times F-DI 16xNAMUR HA Equipment Manual, 10/2024, A5E53588991-AA...
Need help?
Do you have a question about the SIMATIC ET 200SP HA F-DI 16xNAMUR HA and is the answer not in the manual?
Questions and answers