Electrical equipment cannot be installed in Division 1 locations unless they are
intrinsically safe, installed inside approved explosion-proof enclosures, or installed
inside approved purged and pressurized enclosures.
$
&
Division 2 locations are listed below:
Class I volatile flammable liquids or flammable gasses are handled,
• • • •
processed, or used, but confined within closed containers or closed systems
from which they can escape only in cases of accidental rupture or breakdown
of such enclosures or systems, or in case of abnormal operation of
equipment.
Ignitable concentrations of Class I vapors or gasses are normally prevented
• • • •
by positive mechanical ventilation, but which may become hazardous due to
mechanical failure of those ventilation systems.
Location is adjacent to a Division 1 location.
• • • •
Class II combustible dust is not normally in the air in quantities sufficient to
• • • •
produce explosive or ignitable mixtures. Dust accumulations are normally
insufficient to interfere with normal operation of electrical equipment or
other apparatus. Combustible dust may be in suspension in the air as a result
of the following: malfunctioning of handling or processing equipment;
combustible dust accumulations on, or in the vicinity of electrical equipment;
may be ignitable by abnormal operation or failure of electrical equipment.
!
All electrical equipment that is approved for use in Hazardous Locations must
include a group rating. Various flammable and combustible substances are divided
into these groups as a function of their individual maximum experimental safe gap
(MESG), explosion pressure, and ignition temperature.
Component temperatures and the potential for spark based upon voltage, current, and
circuit characteristics, within electrical equipment, will determine what the
equipment group rating will be. A device approved for installation within Class I,
Group A locations may also be used in Groups B, C, or D.
Approved Class I equipment may not be suitable for Class II installations. Class I
includes Groups A, B, C, and D. Class II includes Groups F and G.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Note
Note
26
Chapter 2 – Installation
143448 (D)

Advertisement

Table of Contents
loading

Related Products for Xycom KPM Series

This manual is also suitable for:

Kpmt series5012kpm5012kpmt5015kpm5015kpmt

Table of Contents