Supplementary information

16.4 Configuring with STEP 7

SSL-ID
PROFINET IO
W#16#0D91
Yes
Parameter adr1 changed
No, external interface
W#16#xy92
No
Replacement: SSL-ID
W#16#0x94
W#16#0x94
Yes, internal interface
No, external interface
W#16#0C96
Yes, internal interface
No, external interface
W#16#0591
Yes
Parameter adr1 changed
W#16#0696
Yes, internal interface
No, external interface
Detailed information
For detailed descriptions of the individual system status lists, refer to Manual
Software for S7-300/400 System and Standard Functions
16.4
Configuring with STEP 7
16.4.1

Rules for arranging fault-tolerant station components

The following rules have to be complied with for a fault-tolerant station, in addition to the
rules that generally apply to the arrangement of modules in the S7-400:
● Insert the CPUs into the same slots.
● Redundantly used external DP master interfaces or communication modules must be
inserted in the same slots in each case.
● Insert an external DP master interface for redundant DP master systems only in the
central controllers and not in the expansion units.
● Redundantly used modules (for example, CPU 410-5H, DP slave interface module IM
153-2, external DP interface module CP443-5, communication module CP 443-1) must
be identical, which means they must have the same order number and the same product
or firmware version.
218
PROFIBUS DP
Yes
Yes
Yes, internal interface
No, external interface
Yes, internal interface
No, external interface
Yes
No
Applicability
Module status information of all modules
in the specified rack/station
Rack/station status information
Replace this system status list with the
system status list with ID W#16#xy94 in
PROFIBUS DP, as well.
Rack/station status information
Module status information of a
submodule using the logical address of
this submodule
Module status information for the
interfaces of a module
Module status information of all
submodules on an internal interface of a
module using the logical address of the
module, not possible for submodule 0 (=
module)
.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA
System