Communication service
PROFINET IO
SNMP
(Simple Network
Management Protocol)
Open communication over
TCP/IP
Open communication over
ISO on TCP
Open communication over
UDP
Data record routing
Note
Communication via the PNIO interface
If you want to use the PNIO interface of the module for communication in plant operation,
you must also network this in Step 7 / HW Config / NetPro.
Connection resources in the S7-400 H
S7-400 H components provide a module-specific number of connection resources.
Availability of connection resources
Table 16- 5
Availability of connection resources
CPU
Total number of
connection resources
CPU 410-5H
120
Free S7 connections can be used for any of the above communication services.
Note
Communication service via the PROFIBUS DP interface
A fixed default timeout of 40 s is specified for communication services using S7 connection
resources. If you operate those communication services via a PROFIBUS DP interface at a
low baud rate, operation in configurations with a Ttr (Target Rotation Time) < 20 s is
ensured.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA
Functionality
Data exchange between I/O controllers
and I/O devices
Standard protocol for network
diagnostics and parameter assignment
Data exchange over Industrial Ethernet
with TCP/IP protocol (with loadable
FBs)
Data exchange over Industrial Ethernet
with ISO on TCP protocol (with
loadable FBs)
Data exchange over Industrial Ethernet
with UDP protocol (with loadable FBs)
For example, parameter assignment
and diagnostics of field devices on
PROFIBUS DP with PDM.
Can be used for
S7-H connections
62
Supplementary information
16.6 Communication services
Allocation of S7 connection
resources
No
No
Yes
Yes
Yes
Yes
Reserved from the total number for
PG communication
1
Via DP
Via
PN/IE
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
OP communication
1
223