4. In the "Update Firmware" dialog, select the path to the firmware update files (*.UPD)
5. Click on "Run".
STEP 7 verifies that the selected file can be interpreted by the CPU and then downloads the
file to the CPU. If this requires changing the operating state of the CPU, you will be prompted
to do this in the relevant dialog boxes.
Procedure in SIMATIC Manager
The procedure corresponds to that in HW Config; the menu command here is also "PLC >
Update firmware". However, STEP 7 checks whether the module supports the function only
at the time of execution.
Note
Protecting the update
In order to protect the firmware update, there is a digital signature that is checked by the
CPU during the update. If an error is detected, the old firmware remains active and the new
firmware is rejected.
Values retained after a firmware update
The following values are retained after a CPU memory reset:
● IP address of the CPU
● Device name (NameOfStation)
● Subnet mask
● Static SNMP parameters
9.6

Firmware update in RUN mode

Requirement
You operate the CPU 410-5H in a fault-tolerant system. Both Sync links exist and are
working. There are no I/O bus errors, such as a faulty IM153-2.
Note any information posted in the firmware download area.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA
using the "Browse" button.
After you have selected a file, the information in the bottom boxes of the "Update
Firmware" dialog box indicate the modules for which the file is suitable and from which
firmware version.
Special functions of the CPU 410-5H
9.6 Firmware update in RUN mode
129