Properties and technical specifications of CPU 410 SMART
15.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
Backup battery time, max.
Feed of external backup voltage to the CPU
CPU processing times
CPU speed
PCS 7 process objects
Average processing time of PCS 7 typicals
Process tasks, max.
CPU blocks
DB
Number, max.
FB
Number, max.
FC
Number, max.
OB
Number of free-cycle OBs
Number of time-of-day interrupt OBs
Number of cyclic interrupt OBs
Number of DPV1 interrupt OBs
Number of restart OBs
Number of asynchronous error OBs
Number of synchronous error OBs
Data areas and their retentivity
Retentive data area, total
Address range
I/O address range
Inputs
Outputs
of those distributed
DP interface, inputs
DP interface, outputs
PN interface, inputs
PN interface, outputs
Digital channels
Inputs
Outputs
Analog channels
Inputs
Outputs
206
6ES7410-5HN08-0AB0
Covered with the conditions and effects described in the
Module Data manual
No
450 MHz; multiprocessor system
800; only System Expansion Card PO800 can be used
110 µs; with APL typicals
4; can be set individually from 200 ms to 5 s
16000; number range: 1 to 16 000 (= instances)
8000; number range: 0 to 7999
8000; number range: 0 to 7999
1; OB 1
8; OB 10-17
4; OB 32-35
3; OB 55-57
2; OB 100, 102
9; OB 80-88
2; OB 121, 122
Total work and load memory (with backup battery)
16 KB
16 KB
1536 bytes; up to 1500 IO
1536 bytes; up to 1500 IO
1536 bytes; up to 1500 IO
1536 bytes; up to 1500 IO
36864, max.
36864, max.
2304, max.
2304, max.
CPU 410-5H Process Automation/CPU 410 SMART