2.5
Setting and changing the parameter values
For the details on the parameters, refer to the Instruction Manual of the inverter.
2.5.1
Specifying the parameter number to change the set value
Example: To change the Pr.8 Deceleration time setting from 5 s to 180 s
Display the Quick menu and press
setting mode is activated.
Quick menu
Easy setup wizard
1
Pr. list for App.
Simple Pr. list
PU
STOP
P R E V
LIST
S E T
SET
N E X T
Pr SET
Turn
until [8] appears.
(Or, press
to move [▲] to the target digit, and select the
(→)
parameter number by turning
2
Press
to display the present set value.
(SET)
8 Dec. time
Pres value
Set value
0-3600
BACK
26
FUNCTION AND BASIC OPERATION
. The parameter
(PrSET)
Parameter No.
input
Parameter No.
0000
PU
STOP
P
BACK
S E T
SET
Parameter setting
.)
5.0 sec
5.0 sec
STOP
PU
SET
NEXT
Turn
to set the value to [180.0], and press
value is changed.
3
T
Press
to display the next parameter.
(NEXT)
4
(SET)
8 Dec. time
Pres value
5.0 sec
Set value
180.0 sec
Setting is completed
STOP
PU
BACK
NEXT
9 Rated M Curr/THM
Pres value
4.25A
Set value
4.25A
0-500
STOP
PU
BACK
SET
NEXT
. The set