Inputs / Outputs - Siemens SIMOCODE DP Programming And Operating Manual

Industrial controls, library migration legacy - v9.0 sp2
Hide thumbs Also See for SIMOCODE DP:
Table of Contents

Advertisement

SIMO_CHN Function

3.2 Inputs / Outputs

3.2
Inputs / Outputs
I/O Parameter
Meaning
ADD_F1
operator input: 1=additional function 1
active
ADD_F2
operator input: 1=additional function 2
active
ADDF1_EN
ENABLE: 1=operator may input ADD_F1
ADDF2_EN
ENABLE: 1=operator may input ADD_F2
AUT_L
Linkable Input for Manual/Auto Mode
AUTO_M
1=AUTO_ON1, AUTO_OFF, AUTO_ON2
active 0=AUTO_ON, AUTO_OPT active
AUTO_OFF
AUTO: AUTO_M=1: 1=switch off/stop
AUTO_ON
AUTO: AUTO_M=0: 1=on; 0=off/stop
AUTO_ON1
AUTO: AUTO_M=1: 0->1=switch on
slow/reverse/close
AUTO_ON2
AUTO: AUTO_M=1: 0->1=switch on
fast/forward/open
AUTO_OPT
AUTO: AUTO_M=0:
1=slow/reverse/close;
0=fast/forward/open
AUTON_OP
operator input mode: 1=AUTO;
0=MANUAL
AUTOP_EN
ENABLE: 1=operator may input AUTO
BA_EN
Batch enable
BA_ID
Batch ID
BA_NA
BATCH name
COOL_T
cooling time in [s]
COUNT1
counter 1
COUNT2
counter 2
CS_0
control/signal data (record 130) byte 0
CS_1
control/signal data (record 130) byte 1
CS_2
control/signal data (record 130) byte 2
CS_3
control/signal data (record 130) byte 3
CS_4
control/signal data (record 130) byte 4
CS_5
control/signal data (record 130) byte 5
CS_6
control/signal data (record 130) byte 6
CS_7
control/signal data (record 130) byte 7
CS_8
control/signal data (record 130) byte 8
CS_9
control/signal data (record 130) byte 9
CS_UPD
0->1: update Diagnostic Data
CUR
motor current in %Ie
CUR_AH
HH Alarm LIMIT in %Is
22
Data Type
Default setting Type
BOOL
FALSE
BOOL
FALSE
BOOL
TRUE
BOOL
TRUE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
TRUE
BOOL
FALSE
DWORD
16#0
STRING[32]
''
WORD
16#0
WORD
16#0
WORD
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BYTE
16#0
BOOL
FALSE
REAL
0
REAL
130.0
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
OCM
Permissible
Values
I
+
I
+
I
I
I
I
I
I
I
I
I
I
+
I
I
+
I
+
I
+
O
+
O
O
O
O
O
O
O
O
O
O
O
O
IO
+
O
+
I
+

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simocode dp pcs 7

Table of Contents