SIMO_CHN Function
3.5 Description of Parameters
3.5.2

INBT2 assignment

Assignment of INBT2_01: SIMOCODE-DP check-back signals
The assignment of bits 0.0-0.7 corresponds to the default configuration of SIMOCODE-DP
and should not be changed. The signals are available at the corresponding block outputs
(QON1, QOFF, QON2, QOVL, QLTA, QREMOTE, QG_WRN, QG_FLT).
The assignment of bits 1.0 and 1.1 does not correspond to the default configuration, and
must be completed as required. The signals are available at block outputs QCST and QCTA.
Bits 1.2-1.7 are available for all control functions (except POS), for user-specific assignment
at block outputs Q1_2 - Q1_7. They are not evaluated internally by the block.
For control function POS, additional bits 1.2 and 1.3 must be assigned as required. The
signals are available at block outputs Q1_2 and Q1_3.
Bit
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
36
Meaning
Status On1 - QON1
Status Off - QOFF
Status On2 - QON2
Overload warning - QOVL
Interlock time active - QLTA
Local/Remote - QREMOTE
General fault - QG_FLT
General fault - QG_WRN
Test operation - QCST
Status cooling time active -
QCTA
Only for control function
POS: Status run open -
Q1_2
Only for control function
POS: Status run closed -
Q1_3
Q1_4
Q1_5
Q1_6
Q1_7
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
Configuration in PDM / WinSIMOCODE-DP
Profibus-DP Byte 0 - DP Bit 0.0 Send -> [144] Status On1
Profibus-DP Byte 0 - DP Bit 0.1 Send -> [145] Status Off
Profibus-DP Byte 0 - DP Bit 0.2 Send -> [145] Status On2
Profibus-DP Byte 0 - DP Bit 0.3 Send -> [147] Status
overload warning
Profibus-DP Byte 0 - DP Bit 0.4 Send -> [148] Status lock
time active
Profibus-DP Byte 0 - DP Bit 0.5 Send -> [149] Status
Automatic
Profibus-DP Byte 0 - DP Bit 0.6 Send -> [150] Status general
fault
Profibus-DP Byte 0 - DP Bit 0.7 Send -> [151] Status general
fault
Profibus-DP Byte 1 - DP Bit 1.0 Send -> [157] Status RMT
Profibus-DP Byte 1 - DP Bit 1.1 Send -> [156] Status Cooling
time active
POS: Profibus-DP Byte 1 - DP Bit 1.2 Send -> [158] Status
run open
Otherwise: user-specific assignment
POS: Profibus-DP Byte 1 - DP Bit 1.3 Send -> [159] Status
run closed
Otherwise: user-specific assignment
user-specific assignment
user-specific assignment
user-specific assignment
user-specific assignment