Documentation | EN KL2784/KS2784, KL2794/KS2794 Four channel bus terminals with digital switching outputs, solid state 2021-06-17 | Version: 2.1.0...
, XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners. Patent Pending...
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
49 - week of production 49 YY - year of production 08 - year of production 2008 FF - K-bus firmware version 1B - firmware version 1B HH - hardware version 03 - hardware version 03 KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
The output is short-circuit-proof to a limited extent. The output transistor can cope with short- term overcurrents until the fuse is triggered. The Bus Terminal contains four channels that indicate its signal state by means of light emitting diodes. Version: 2.1.0 KL2784/KS2784, KL2794/KS2794...
The output is short-circuit-proof to a limited extent. The output transistor can cope with short-term overcurrents until the fuse is triggered. The Bus Terminal has four channels, whose signal state is displayed by LEDs. KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
EN 61000-6-2 / EN 61000-6-4 Protection class IP20 Pluggable wiring for all KSxxxx terminals Correct installation position variable Approvals / markings CE, cULus [} 21], ATEX Ex marking Standard Marking ATEX II 3 G Ex nA IIC T4 Gc Version: 2.1.0 KL2784/KS2784, KL2794/KS2794...
Signal LED 1 Output 1 switched off Output 1 switched on Signal LED 2 Output 2 switched off Output 2 switched on Signal LED 3 Output 3 switched off Output 3 switched on Signal LED 4 Output 4 switched off Output 4 switched on KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
• Each assembly must be terminated at the right hand end with a KL9010 bus end terminal, to ensure the protection class and ESD protection. Fig. 3: Spring contacts of the Beckhoff I/O components Version: 2.1.0 KL2784/KS2784, KL2794/KS2794...
To mount the mounting rails with a height of 7.5 mm under the terminals and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets). KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
EL91xx, EL92xx) interrupt the power contacts and thus represent the start of a new supply rail. PE power contact The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first when plugging together, and can ground short-circuit currents of up to 125 A. Version: 2.1.0 KL2784/KS2784, KL2794/KS2794...
Power Feed Terminals can be released and pulled at least 10 mm from the group of terminals. WARNING Risk of electric shock! The PE power contact must not be used for other potentials! KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
Insert the new component and plug in the connector with the wiring. This reduces the installation time and eliminates the risk of wires being mixed up. The familiar dimensions of the terminal only had to be changed slightly. The new connector adds about 3 mm. The maximum height of the terminal remains unchanged. Version: 2.1.0 KL2784/KS2784, KL2794/KS2794...
Ultrasonically “bonded” (ultrasonically welded) conductors Ultrasonically “bonded” conductors It is also possible to connect the Standard and High Density Terminals with ultrasonically “bonded” (ultrasonically welded) conductors. In this case, please note the tables concerning the wire-size width! KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
The cables are released, as usual, using the contact release with the aid of a screwdriver. See the following table for the suitable wire size width. Version: 2.1.0 KL2784/KS2784, KL2794/KS2794...
Load 2 0 V 0 V (internally connected to terminal points 2, 3, 7 and power contact for 0 V) 0 V 0 V (internally connected to terminal points 2, 3, 6 and power contact for 0 V) Output 4 Load 4 KL2784/KS2784, KL2794/KS2794 Version: 2.1.0...
80°C at the wire branching points, then cables must be selected whose tempera- ture data correspond to the actual measured temperature values! • Observe the permissible ambient temperature range of 0 to 55°C for the use of Beckhoff fieldbus compo- nents standard temperature range in potentially explosive areas! •...
IECEx Pay also attention to the continuative documentation Ex. Protection for Terminal Systems Notes on the use of the Beckhoff terminal systems in hazardous areas according to ATEX and IECEx that is available for download on the Beckhoff homepage www.beckhoff.com! Version: 2.1.0...
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: https://www.beckhoff.com You will also find further documentation for Beckhoff components there.
Page 24
Fig. 1 KL2794 - Bus terminal, 4-channel solid state output, 30 VAC, 48 VDC, 2 A, potential-free..Fig. 2 LED display..........................Fig. 3 Spring contacts of the Beckhoff I/O components................. Fig. 4 Attaching on mounting rail ......................Fig. 5 Disassembling of terminal......................Fig. 6 Power contact on left side......................