Line Module Control; Line Module Control Aoi - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4 SINAMICS S120 Add-On Instructions
4.7

Line Module Control

4.7.1
Functionality
The line module control AOI allow for simple control and monitoring of a line
module for the S120 drives. The line module can be enabled via AOI inputs and an
output signals the current state. Faults are monitored and can be acknowledged
via input.
4.7.2
Schematic Ladder representation
Figure 4-5 Line Module Control AOI
Table 4-17 Inputs Parameters
Variable Name
S120_LineModule
Enable
OFF2
FaultAck
DRV_STATUS
Table 4-18 Output Parameters
Variable Name
Ready
Enabled
Inhibited
FaultActive
AlarmActive
DRV_CONTROL
SINAMICS S: Speed control of a S120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP
Entry-ID: 92045369,
V4.0,
Data Type
Instance Data
BOOL
BOOL
BOOL
WORD
Data Type
BOOL
BOOL
BOOL
BOOL
BOOL
WORD
08/2018
Description
Enable the Line Module
1 = Enable
0 = Disable Drive
Immediate Pulses Disable
1 = Allow Pulse Enable
0 = Disable Pulses
Acknowledge Active Faults
0 -> 1 Acknowledge Faults
Status Data from IO mapped to Line Module
Description
Line Module is Ready
Line Module is Precharged and Enabled
Operation Inhibited
Fault is Active
Alarm is Active
Control Data to IO mapped to Line module
18