Install the S5000 Chassis in a Rack or Cabinet
To install the S5000 system, Dell Networking recommends completing the installation procedures in the
order presented here.
NOTE: Always handle the system and its components with care. Avoid dropping the S5000 chassis or its field
replaceable units.
NOTE: For proper ventilation, position the S5000 chassis in an equipment rack (or cabinet) with a minimum of 5
inches (12.7 cm) of clearance around exhaust vents. The acceptable ambient temperature ranges are listed in the
Environmental Parameters section.
CAUTION: Always wear an ESD-preventive wrist or heel ground strap when handling the S5000 and its
components. As with all electrical devices of this type, take all necessary safety precautions to prevent injury
when installing this system. ESD damage can occur if components are mishandled.

Attaching the Mounting Brackets

The S5000 is shipped with mounting brackets (rack ears) and the required screws (eight screws) for rack or cabinet
installation. The brackets are enclosed in a package with the chassis.
1.
Take the brackets and screws out of their packaging.
2.
Slide the mounting brackets, as shown in the following figure.
Figure 9. Slide the mounting brackets
1. Utility side of the chassis
2. Mounting Bracket
3. Holding Bracket (factory installed)