Deployment I/O periphery
Diagnostic and interrupt > Diagnostic interrupt
150
Byte
Bit 7...0
0 ... 3
Content record set 0
4
n
Bit 6 ... 0: Channel type (here 70h)
70h: Digital input
71h: Analog input
72h: Digital output
73h: Analog output
74h: Analog input/output
n
Bit 7: More channel types present
0: no
1: yes
5
Number of diagnostic bits per channel (here 08h)
6
Number of channels of a module (here 08h)
7
n
Bit 0: Error in channel group 0 (I+0.0 ... I+0.3)
n
Bit 1: Error in channel group 1 (I+0.4 ... I+0.7)
n
Bit 2: Error in channel group 2 (I+1.0 ... I+1.3)
n
Bit 3: Error in channel group 2 (I+1.4 ... I+1.7)
n
Bit 4: Error in channel group 4 (counter 0)
n
Bit 5: Error in channel group 5 (counter 1)
n
Bit 6: Error in channel group 6 (counter 2)
n
Bit 7: reserved
8
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: ... input I+0.0
n
Bit 1: 0 (fix)
n
Bit 2: ... input I+0.1
n
Bit 3: 0 (fix)
n
Bit 4: ... input I+0.2
n
Bit 5: 0 (fix)
n
Bit 6: ... input I+0.3
n
Bit 7: 0 (fix)
9
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: ... input I+0.4
n
Bit 1: 0 (fix)
n
Bit 2: ... input I+0.5
n
Bit 3: 0 (fix)
n
Bit 4: ... input I+0.6
Bit 5: 0 (fix)
n
Bit 6: ... input I+0.7
n
n
Bit 7: 0 (fix)
10
Diagnostic interrupt due to "process interrupt lost" at...
n
Bit 0: ... input I+1.0
n
Bit 1: 0 (fix)
n
Bit 2: ... input I+1.1
Bit 3: 0 (fix)
n
Bit 4: ... input I+1.2
n
n
Bit 5: 0 (fix)
n
Bit 6: ... input I+1.3
n
Bit 7: 0 (fix)
Ä 'Record set 0 Diagnostic