Advertisement

Caution
Signal cables must not be routed parallel to power cables.
Overview of the DC link supply adapter and DC link adapter
DC link supply adapter (cable outlet on top)
6SL3162-2BD00-0AAx
6SL3162-2BM00-0AAx
DC link adapter (cable outlet on side)
6SL3162-2BM01-0AAx
Note
The current carrying capacity of the DC link busbars must be taken into account. For the
specifications, see the technical specifications for the module.
Equipment Manual Booksize Cold-Plate Power Sections
Manual, (GH4), Edition 06.2005, 6SL3097-2AJ00-0BP2
Suitable for module width:
50 mm, 100 mm
150 mm, 200 mm, 300 mm
all
12.4 Arrangement of Components and Equipment
Max. connectable cross-
section
10 mm
2
95 mm
2
95 mm
2
Cabinet Design and EMC
Max. current carrying capacity
36 A
240 A
240 A
12-17