Siemens SINAMICS S120 Equipment Manual page 20

Booksize power sections cold plate
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Description
1.2 System Data
Information on storage, transportation and operation:
Environmental class
Storage
Transportation
Operation
Organic/biological influences
Storage
Transportation
Operation
Vibratory load
Transportation
Operation
Shock load
Transportation
Operation
Climatic ambient conditions
Storage
Transportation
Operation
Degree of contamination
Installation altitude
Approbation
Certification
1-4
Class 1C2 to EN 60 721-3-1
Class 2C2 to EN 60 721-3-2
Class 3C2 to EN 60 721-3-3
Class 1B1 to EN 60 721-3-1
Class 2B1 to EN 60 721-3-2
Class 3B1 to EN 60 721-3-3
EN 60 721-3-2, class 2M3
EN 60 721-3-3, class 3M4
EN 60 721-3-2, class 2M3
EN 60 721-3-3, class 3M3
Class 1K3 to EN 60 721-3-1
Temperature: -40 °C to +70 °C
Class 2K4 to EN 60 721-3-2
Temperature: -40 °C to +70 °C
Max. humidity: 95 % at 40 °C
Class 3K3 to EN 60 721-3-3
Relative air humidity 5 to 65 % (annual average,
≦ 80 % above the maximum for 2 months a year.
Avoid splashing water and do not allow condensation or ice
to form (EN 60 204, Part 1)
2 to EN 60 664-1
Up to 1,000 m above sea level without derating,
>1,000 m to 5,000 m above sea level (see derating
characteristics)
CE (low-voltage and EMC Directives), cULus
(file pos.: E192450, E164110, E70122, and E214113)
Equipment Manual Booksize Cold-Plate Power Sections
Manual, (GH4), Edition 06.2005, 6SL3097-2AJ00-0BP2

Advertisement

Table of Contents
loading

Table of Contents