Omron CPM2C Operation Manual page 55

Hide thumbs Also See for CPM2C:

Advertisement

4
Life (x 10
)
Transistor Outputs (Sinking or Sourcing)
Item
Max. switching capacity
Min. switching capacity
Max. inrush current
Leakage current
Residual voltage
ON delay
OFF delay
Fuse
Note The service life of relay output contacts shown in the table assumes the worst
conditions. The following graph shows the results of OMRON's service life tests
at a switching rate of 1,800 times/hour.
120 VAC, resistive load
24 VDC, τ = 7 ms
120 VAC, cosφ = 0.4
240 VAC, cosφ = 0.4
24 VDC/240 VAC, resistive load
40 mA/4.5 VDC to 300 mA/20.4 VDC,
300 mA (20.4 VDC to 26.4 VDC)
When using OUT01000 or OUT01001 as a pulse output, connect a dummy resistor as
required to bring the load current between 10 and 150 mA. If the load current is below
10 mA, the ON/OFF response time will be longer and high-speed pulses will not be output.
The transistor will heat if used at 150 mA or higher, possibly damaging elements.
0.5 mA
0.9 A for 10 ms (charging and discharging waveform)
0.1 mA max.
0.8 V max.
OUT01000 and OUT01001:
OUT01002 and up:
OUT01000 and OUT01001:
OUT01002 and up:
1 fuse for each 2outputs (cannot be replaced by user)
Switching rate: 1,800 times/hour
Contact current (A)
Specification
20 µs max.
0.1 ms max.
40 µs max. 10 to 300 mA
0.1 ms max. 0.5 to 10 mA
1 ms max.
Section
2-2