Chapter 3 – Electrical Installation
Inverter Modules of
Frame Sizes R2i to R5i
(ACS 600 MulitDrive)
F10
Connect separate PE
conductor (if used) to the PE
terminal of the cabinet
Control cable connection:
Connect the control cables to the
appropriate terminal block on the DIN rail.
3-18
The cable connections of a bottom entry unit are represented below.
For top exit, an extra cabinet is required.
PE terminal of
the cabinet
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
Motor cable connection
1. Strip the cable for 3 cm at the cabinet entry if
EMC sleeves are used.
2. Lead the cable unstripped to the inverter
module.
If connection terminals are outside the module,
make the connections like this:
PE PE U2 V2 W2
Tighten the screw to the torque given in ACS 600
MultiDrive Safety and Product Information,
Appendix A.
If connection terminals are inside the module,
1. remove the module cover.
2. make the connections:
OUTPUT
U2 V2 W2
Tighten the screw to the torque given in ACS 600
MultiDrive Safety and Product Information,
Appendix A.
.
module PE