Optical Components - ABB ACA 6 Series Hardware Manual

Frequency converters 3 to 4300 kw
Table of Contents

Advertisement

Optical Components

DDCS
Channel
NAMC-11/51 Board
CH0
-
CH1
5 MBd
CH2
-
CH3
-
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
Observe colouring codes when installing fibre optic cables. Blue
connectors should go to blue terminals, and grey connectors to grey
terminals.
In case multiple modules are installed on the same channel, they must
be connected in a ring.
The optical transmitter and receiver types (5 MBd or 10 Mbd) in DDCS
channels CH0 to CH3 on the NAMC boards are given below.
Optical Transmitter/Receiver Type
DDCS Communication Option
NDCO-01
NDCO-02
10 MBd
5 MBd
(DriveBus)
-
-
10 MBd
10 MBd
10 MBd
10 MBd
Note 1: When connecting an NAMC board to another unit make sure,
that the optical components are of the same type at both ends of the
link. Do not mix 5 MBd and 10 MBd transmitters and receivers.
Note 2: With 5 MBd optical components only plastic optical cable
(POF) can be used. The maximum cable length is 10 metres.
However, when operating at the lower speed of 1 Mbit/s (normally with
DriveWindow) the cable length can be extended to 15 metres.
Note 3: With 10 MBd components either plastic (POF) or Hard
Clad Silica (HCS) optical cable can be used. When the maximum
optical power (transmitter current) is selected by the software, the
following cable lengths are applicable:
Cable
POF
HCS
Chapter 3 – Electrical Installation
NAMC-21 Board
NDCO-03
5 MBd
10 MBd (DriveBus)
-
5 MBd
5 MBd
10 MBd
5 MBd
10 MBd
NAMC-21/22/51 Board
Cable length (m)
30
200
NAMC-22 Board
5 MBd
5 MBd
10 MBd
10 MBd
3-39