Board Installation - Honeywell Notifier MODBUS-GW Installation And Operation Manual

Modbus gateway
Table of Contents

Advertisement

Board Installation

2.2 Board Installation
The MODBUS-GW may be installed in a CAB-3 or CAB-4 cabinet as shown below.
Board
Install bracket on 1/2" standoffs. Place the board's
tab in the bracket slot and screw the board to the
top of the standoffs. May be stacked in front of or
behind another board using standoffs of adequate
length to clear the rear board.
Figure 2.1 NFS-320 Series Installation
Screws
Slot
Figure 2.3 CHS-4L Installation
MODBUS-GW Installation and Operation Manual — P/N LS10015-000NF-E:C2 4/30/2019
Keypad Removed
Bracket Slot
Tab
Three Possible Mounting
Positions - Rear Only
Board
Mount in 4th column of the NFS2-640 Series
chassis. Mount chassis to backbox before installing
the board in rear position. May be mounted in front
of another board using standoffs of adequate length
to clear the rear board.
Figure 2.2 NFS2-640 Series Installation
Board Grounding Area
Screws
Figure 2.4 Securing the Board
Installation
Mounting Studs
Slot
15