Zones/Panel Circuits Status Holding Registers - Honeywell Notifier MODBUS-GW Installation And Operation Manual

Modbus gateway
Table of Contents

Advertisement

Register Mapping

5.4 Zones/Panel Circuits Status Holding Registers

Each of the zones/panel circuits status holding registers are divided into an upper and lower byte as described below and in
• Upper Byte: The upper byte contains general status information about the zone or panel circuit.
• Lower Byte: The lower byte is primarily used when bit 11 in the upper byte is a '1' (or active). When bit 11 is a '1', refer to
Appendix C, "MODBUS-GW Active Event Types"
byte will be all 0's if the zone/panel circuit is not in an active state.
Specifically, the lower byte contains the actual active event for this zone or panel circuit. An active state is defined in this
gateway as any Fire, Security, Critical Process, Medical, Mass Notification, or Supervisory alarm state. If the zone or panel
circuit is not present in the panel programming, all bits in the lower byte will contain a '1' or the value 'FFH'.
Bit No.
Bit Name
Ack Block
When individual upper byte bits are set to 1, the following definitions apply:
• Ack Block (Bit 15): All events on this zone/panel circuit, other than fire alarm, are
• Prealarm (Bit 14): The zone/panel circuit is in a prealarm state.
• Trouble (Bit 13): The zone/panel circuit is in a trouble state.
• InActive (Bit 12): The zone/panel circuit is not active.
• Active (Bit 11): The zone/panel circuit is active and there will be an active event type
• Enable (Bit 10): The zone/panel circuit is enabled.
• Disable (Bit 9): The zone/panel circuit is disabled.
• Ack Fire Alarm (Bit 8): The fire alarm on this zone/panel circuit is acknowledged.
The holding register addresses and the zones contained in these addresses are detailed in
General Zones
Logic Zones
Trouble Zones
Releasing Zones
34
Table 5.5 Zones/Panel Circuits Holding Register Bit Definitions
15
14
13
Prealarm
Trouble
acknowledged.
in the lower byte.
Zone Type
MODBUS-GW Installation and Operation Manual — P/N LS10015-000NF-E:C2 4/30/2019
for detailed information about the active zone or panel circuit. The lower
Upper Byte
12
11
10
InActive
Active
Enable
Disable
Table 5.6 Zones
Register Address
46001–47000
47001–49000
49001–49100
49101–49110
Zones/Panel Circuits Status Holding Registers
9
8
7 6 5 4 3 2 1 0
Ack Fire Alarm
Active Event Type
(When Bit 11 is set to 1,
see Appendix C.)
Table
5.6.
Zone Address
Z 1,2,3,4,5,6,7,8,...1000
Z 1,2,3,4,5,6,7,8,...2000
Z 1,2,3,4,5,6,7,8,...100
Z 1,2,3,4,5,6,7,8,9,10
Table
5.5.
Lower Byte