Siting and levelling the boiler
!
Please note
Damage to the flue gas connection can result in
leaks.
Never lift or move the boiler by the flue gas con-
nection.
Information on handling
Hook lifting gear for transport by crane into the holes in
the front and back panel of the boiler.
A
Fig. 2
Note
A suitable condensate drain must be available in the
installation room. If the boiler is installed at ground
level, the condensate drain must be no more than
50 mm above floor level. Otherwise install a conden-
sate removal pump.
Adjusting screws
pack.
Recommendation:
Position the boiler on adjustable anti-vibration feet
(accessories). Insert adjustable feet into the base rails
from below.
2.
1.
are supplied in the accessory
A
7