Initializing the detector

4.9 Initializing the detector
32 | 44
After the fine-tuning of the detector optics, the detector must be initialized with the
hood screwed on.
1
Figure 25: Initializing the detector
1 End plug
2 Bushes
w
The detector line is switched on.
w
Setting of the detector optics is complete.
1. Remove the sealing plug (1) from the hood.
2. Connect the MC link cable to the socket (2) of the detector.
a
The standardized signal value and the detection distance are displayed in
the 'Adjust' menu on the adjustment device. Example:
1133
50m
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
values
distance
[m]
date &
action
3. Copy the two display values onto the two labels.
2
3 Button
Adjust
signal-
deviate-
covered-
value
signal
reflector
[-]
[%]
value
[%]
50 1133
3
A6V10332811_e_en_--

Advertisement