Commissioning
4
Set parameter set
22 | 44
Parameter set
No. Name
04
Sensitive with British
Standard Alarm
05
Very sensitive with
open line
06
Very sensitive with
British Standard Alarm
Table 1: Set parameter set
Parameter set 2 meets the requirements of standard EN 54‑12.
DIP switch
Alarm for n %
1
attenuation
50 %
OFF
30 %
ON
40 %
OFF
2
3
4
5
6
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF