Commissioning
4
Installing the detector heating unit (optional)
4.3 Installing the detector heating unit (optional)
4.4 Inserting the filter in detector (optional)
24 | 44
You must install the detector heating unit DLH1191A if there is a danger of
moisture condensation. To do this, you need a 24 V supply.
1. Insert the detector heating unit in the detector.
2. Connect the detector heating unit to the printed circuit board.
Figure 19: Installation of the detector heating unit
For short detection distances and strong extraneous light, you may have to use a
filter.
1. Select the filter according to the planning information:
–
Short distance filter DLF1191-AA
–
Short distance filter DLF1191-AB
–
Extraneous light filter DLF1191-AC
2. Insert the filter (1) in the detector.
1
Figure 20: Inserting the filter
A6V10332811_e_en_--