Siemens FDL241-9 Mounting, Commissioning

Siemens FDL241-9 Mounting, Commissioning

Linear smoke detector
Hide thumbs Also See for FDL241-9:

Advertisement

Quick Links

FDL241-9
Linear smoke detector
Mounting
Commissioning
Smart Infrastructure
A6V10332811_e_en_--
2019-06-18

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FDL241-9

  • Page 1 FDL241-9 Linear smoke detector Mounting Commissioning Smart Infrastructure A6V10332811_e_en_-- 2019-06-18...
  • Page 2 All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724-2424 www.siemens.com/buildingtechnologies Edition: 2019-06-18 Document ID: A6V10332811_e_en_-- © Siemens Switzerland Ltd, 2011 2 | 44 A6V10332811_e_en_--...
  • Page 3: Table Of Contents

    Table of contents About this document................. Structure and function ................Overview....................Function....................2.2.1 Infrared ray ................. Reflectors ....................Mounting / Installation................Switching detector over to collective operation ........Installing the detector base............... Electrical connection................. 3.3.1 Connection to an addressed detector line ........3.3.2 Connection to a collective detector line ........
  • Page 4 6.12 Alarm test filter TF04 ................6.13 M20 x 1.5 metal cable gland..............4 | 44 A6V10332811_e_en_--...
  • Page 5: About This Document

    In accordance with EN 62471, 'Photobiological Safety of Lamps and Lamp Systems', the linear smoke detector falls into the 'Exempt Group'. Applicable documents Document ID Title 007016 Technical manual Linear smoke detector FDL241-9 007017 Data sheet ASA Linear smoke detector FDL241-9 A6V10332811_e_en_-- 5 | 44...
  • Page 6: Structure And Function

    Structure and function Overview 2 Structure and function 2.1 Overview The linear smoke detector FDL241‑9 detects fires according to the principle of light attenuation by smoke. The linear smoke detector works together with a reflector, which is installed opposite the detector. Properties ●...
  • Page 7: Infrared Ray

    Structure and function Overview When smoke is present, part of the infrared ray is absorbed when it encounters the smoke particles, while another part is scattered by smoke particles. The rest reaches the reflector and is returned to the receiver. The infrared ray is attenuated further.
  • Page 8 Structure and function Overview ● Effective range (1): The effective range is the connection between the transmitter, reflector and receiver. ● Core range (2): In the core, enough radiation energy is present to operate the system. ● Scattering range (3): The radiation energy in the scattering range is insufficient and does not ensure the functionality of the system.
  • Page 9 Structure and function Overview One turn of the knurled screw moves the infrared ray by approx. 0.8 m per 100 m distance. 10° 10° 100 m Figure 5: Horizontal adjustment range 1 Diameter of the core 5° 5° 100 m Figure 6: Vertical adjustment range 1 Diameter of the core A6V10332811_e_en_-- 9 | 44...
  • Page 10: Reflectors

    Structure and function Reflectors 2.3 Reflectors Retro-reflectors reflect rays of light that reach them in parallel. The reflector does not necessarily have to be installed at a right angle to the ray of light. Vibrations and distortions on the mounting surface do not interfere with this. Interfering light is also reflected in parallel and does not therefore reach the receiver.
  • Page 11: Mounting / Installation

    Mounting / Installation Switching detector over to collective operation 3 Mounting / Installation Prerequisites ● The installation locations for the detector and reflector are defined according to the planning information. ● The supply network is produced, connected and checked in line with the country-specific installation guidelines. Sequence 1.
  • Page 12: Installing The Detector Base

    Mounting / Installation Installing the detector base Figure 9: Connection diagram for the source of DC voltage 3.2 Installing the detector base WARNING Danger of falling Bodily injury ● When installing, use a secured ladder or work platform. CAUTION Using the device in a damp and/or corrosive environment Device function is impaired.
  • Page 13 Mounting / Installation Installing the detector base 4. Guide the cables from the detector line and external alarm indicator into the detector base. You will also need a 24 V supply if you are using the detector heating unit DLH1191A. 5. Mount the carrier (2) for the connection terminals by inserting two screws into the detector base.
  • Page 14: Electrical Connection

    Mounting / Installation Electrical connection 3.3 Electrical connection ● Specialist electrical engineering knowledge is required for installation. ● Only an expert is permitted to carry out installation work. Incorrect installation can take safety devices out of operation unbeknown to a layperson. The electrical connection depends on the following factors: ●...
  • Page 15 Mounting / Installation Electrical connection ● Loops, stubs and T-branches are possible. ● You may only connect external alarm indicators to one detector. ● Permissible cables for detectors with more than one external alarm indicator according to the collective connection diagram may be migrated to the FDnet/ C-NET without any changes.
  • Page 16 Mounting / Installation Electrical connection There are two ways of connecting external alarm indicators: LINE LINE LINE LINE LINE LINE Figure 13: Connection diagram for addressed detector line with and without external alarm indicators (with shielded cables) 1 Control panel 3 Auxiliary terminals DBZ1190‑xx 2 Detector 4 External alarm indicator Variant A...
  • Page 17: Connection To A Collective Detector Line

    Mounting / Installation Electrical connection 3. Connect each of the two negative poles of the external alarm indicator separately to both negative poles of the detector line. The two negative connections of the external alarm indicator are decoupled externally in the alarm indicator by diodes. 4.
  • Page 18 Mounting / Installation Electrical connection 3.3.2.2 Use of shielded cables The detector line shielding must be connected through in the detector base with auxiliary terminals DBZ1190-xx. There are two ways of connecting external alarm indicators: LINE LINE LINE LINE LINE Figure 15: Connection diagram for collective detector line with and without external alarm indicators (with shielded cables) 1 Control panel 4 External alarm indicator...
  • Page 19: Installing The Reflector For Long Distance (Prism)

    Mounting / Installation Installing the reflector for long distance (prism) 3.4 Installing the reflector for long distance (prism) WARNING Danger of falling Bodily injury ● When installing, use a secured ladder or work platform. Figure 16: Installing the reflector 1 Base 3 Terminals for heating 2 Prism unit Mounting without heating unit The mounting location of the reflector is defined according to the planning...
  • Page 20: Installing The Reflectors For Middle Distance And Short Distance (Foil)

    Mounting / Installation Installing the reflectors for middle distance and short distance (foil) 5. Connect the wires to the terminals for the heating unit (3) according to the connection diagram. 6. Install the prism unit (2) on the base with four screws. 3.5 Installing the reflectors for middle distance and short distance (foil) WARNING Danger of falling...
  • Page 21: Commissioning

    Commissioning Set parameter set 4 Commissioning Sequence 1. Set parameter set 2. Install detector unit 3. Install detector heating unit (optional) 4. Insert filter in detector (optional) 5. Commissioning the adjustment device 6. Checking the signal level and distance 7. Preliminary setting of the detector optics (optional) 8.
  • Page 22 Commissioning Set parameter set Parameter set DIP switch No. Name Alarm for n % attenuation Sensitive with British 50 % Standard Alarm Very sensitive with 30 % open line Very sensitive with 40 % British Standard Alarm Table 1: Set parameter set Parameter set 2 meets the requirements of standard EN 54‑12. 22 | 44 A6V10332811_e_en_--...
  • Page 23: Installing The Detector Unit

    Commissioning Installing the detector unit 4.2 Installing the detector unit WARNING Danger of falling Bodily injury ● When installing, use a secured ladder or work platform. The carrier for connection terminals is mounted in the detector base. 1. Insert the detector unit (1) into the base (2) along with the carrier for the connection terminals with the LED pointing downwards.
  • Page 24: Installing The Detector Heating Unit (Optional)

    Commissioning Installing the detector heating unit (optional) 4.3 Installing the detector heating unit (optional) You must install the detector heating unit DLH1191A if there is a danger of moisture condensation. To do this, you need a 24 V supply. 1. Insert the detector heating unit in the detector. 2.
  • Page 25: Commissioning The Adjustment Device

    Commissioning Commissioning the adjustment device 4.5 Commissioning the adjustment device Securing the adjustment device to the detector 1. From the adjustment set, take the chain with the two cable grippers and the snap hook. 2. Screw one cable gripper into a free opening for the cable entry (1) on the detector base.
  • Page 26 Commissioning Commissioning the adjustment device Indication location Example Meaning Top left Signal level before initialization The signal level must be between 255 and 1195 for initialization. Otherwise initialization is not possible. 100 % Standardized signal value as % of the current compensation value During initialization, the signal level is equalized to the compensation value 100 %.
  • Page 27: Checking The Signal Level And Distance

    Commissioning Checking the signal level and distance 4.6 Checking the signal level and distance The detector line is switched on. 1. Loosen the two safety screws (3). 2. Make sure that the vertical scale (7) and the horizontal scale (1) are centered (factory setting).
  • Page 28 Commissioning Checking the signal level and distance Adjust See also Preliminary setting of the detector optics (optional) [➙ 29] Fine-tuning of the detector optics [➙ 30] 28 | 44 A6V10332811_e_en_--...
  • Page 29: Preliminary Setting Of The Detector Optics (Optional)

    Commissioning Preliminary setting of the detector optics (optional) 4.7 Preliminary setting of the detector optics (optional) Preliminary setting of the detector optics must only undertaken when the signal level was below 100 and/or the distance indication was incorrect. The detector line is switched on. The adjustment device is connected to the detector and must be set to 'Adjust'.
  • Page 30: Fine-Tuning Of The Detector Optics

    Commissioning Fine-tuning of the detector optics 4.8 Fine-tuning of the detector optics Figure 24: Fine-tuning with the adjustment device 1 Knurled screw for horizontal 6 Adjustment device adjustment 2 Safety screws 7 Bushes 3 Hood 8 Knurled screw for vertical adjustment 4 Alarm indicator 9 Opening for cable entry...
  • Page 31 Commissioning Fine-tuning of the detector optics The adjustment device is connected to the detector and must be set to 'Adjust'. The two safety screws (2) are loosened. 1. Turn the knurled screws (1, 8) until the standardized signal value on the adjustment device is as high and constant as possible (point A in the figure above).
  • Page 32: Initializing The Detector

    2. Connect the MC link cable to the socket (2) of the detector. The standardized signal value and the detection distance are displayed in the 'Adjust' menu on the adjustment device. Example: Adjust 1133 FDL241-9; commissioning & adjustment data (values displayed on adjustment device) values distance signal-...
  • Page 33 Following successful initialization, 100 % ±3 % and the effective detection distance is displayed on the adjustment device. Example: 100% 5. Copy the standardized signal value onto the two labels. 100% FDL241-9; commissioning & adjustment data (values displayed on adjustment device) values distance signal-...
  • Page 34: Testing Detectors

    1. Cover the reflector completely, using an appropriate object. The standardized signal value on the adjustment device must be <5 %; the distance display is frozen. 2. Enter the read-in standardized signal value on the two labels. FDL241-9; commissioning & adjustment data (values displayed on adjustment device) values distance...
  • Page 35: Specifications

    Specifications Technical data 5 Specifications 5.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: ● Document 007017 Addressed detector line (FDnet/C-NET) Detector line Operating voltage DC 12...33 V...
  • Page 36 Specifications Technical data Reset voltage DC 2…4 V Reset time at reset voltage DC 2 V 1…2 s Protocol Collective (with and without current limitation) Compatibility See 'List of compatibility' Addressed detector line and collective detector line External alarm indicators Number of external alarm indicators that can be connected Voltage DC 6…17 V...
  • Page 37 Specifications Technical data Connections Detector line, detector heating unit and external alarm indicator: ● Design Socket strip ● Conductor cross section 0.2…1.5 mm MC link Plug-type connection (3.5 mm jack) Ambient conditions Operating temperature -25…+60 °C Operating temperature checked in -10…+55 °C accordance with EN 54‑12 Storage temperature -30…+75 °C Air humidity...
  • Page 38: Dimensions

    Specifications Dimensions 5.2 Dimensions Base for linear smoke detector FDLB291 Base for linear smoke detector FDLB291 with linear smoke detector FDL241‑9 M20 x 1.5 Reflector for long distance (prism) DLR1191 M20 x 1.5 Reflector for middle distance (foil) DLR1192 and reflector for short distance (foil) DLR1193 100 / 200 38 | 44...
  • Page 39: Environmental Compatibility And Disposal

    Specifications Environmental compatibility and disposal 5.3 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken: ● Use of reusable materials ●...
  • Page 40: Details For Ordering

    6.2 Base for linear smoke detector FDLB291 ● For installing the linear smoke detector ● Compatible with: – Linear smoke detector FDL241-9 ● Order number: A5Q00003941 See also Installing the detector base [➙ 12] 6.3 Reflector for long distance (prism) DLR1191 ●...
  • Page 41: Reflector For Middle Distance (Foil) Dlr1192

    Dimensions: 200 x 200 x 2.5 mm ● Hole diameter: 4 mm ● Compatible with: – Linear smoke detector FDL241-9 ● Order number: BPZ:4788490001 See also Installing the reflectors for middle distance and short distance (foil) [➙ 20] 6.5 Reflector for short distance (foil) DLR1193 ●...
  • Page 42: Short Distance Filter Dlf1191-Ab

    For toning down the infrared ray over short distances ● Distance: 5…8 m ● Compatible with: – Linear smoke detector FDL241-9 ● Order number: BPZ:4933160001 6.8 Extraneous light filter DLF1191-AC ● For filtering extraneous light during a high level of extraneous light ●...
  • Page 43: Detector Tester For Linear Smoke Detector Re10

    ● For undertaking a performance check on the linear smoke detector ● Compatible with: – Linear smoke detector FDL241-9 ● Order number: BPZ:3685190001 6.12 Alarm test filter TF04 ● Alarm test filter for detector tester for linear smoke detector RE10 ●...
  • Page 44 © Siemens Switzerland Ltd, 2011 Issued by Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies A6V10332811_e_en_--...