Emergency Operation; Response Characteristics Of The Detector; Environmental Influences; Influence Of The Ambient Air Temperature - Siemens Cerberus DOT1151A-Ex Technical Description

Neural smoke detector, interactive, intrinsically safe
Table of Contents

Advertisement

6

Emergency operation

If the PolyRex detector DOT1151-Ex can no longer be periodically addressed, for example
due to a µP failure in the control unit, the detectors switch automatically to emergency op-
eration. In the event of a fire this detector can still trigger a collective alarm.
7
Response characteristics of the
detector
The PolyRex detector DOT1151-Ex is equipped with efficient algorithms for discriminating
between true fires and deceptive phenomena. To signal a danger level the detector does
not simply respond to a reading above a «response threshold», but rather tracks the smoke
density pattern over a longer period of time and evaluates it with appropriate algorithms.
The software parameters determine the response behavior of the detectors. They are de-
pendent on the risk prevailing at the installation site (on the selected parameter set) and on
the activated operating mode (day, night, special [renovation], test and switched off).
The current operating mode is signalled to the detectors by the control unit in intervals of
approx. 3 seconds.
The algorithms contain, for example, filters for suppressing transient interference vari-
ables. Slow changes caused by contamination are compensated by the automatic digital
compensation circuit. This extremely slow compensation ensures that also slowly develop-
ing fires are reliably detected.
8

Environmental influences

8.1

Influence of the ambient air temperature

The smoke sensitivity of the PolyRex detector DOT1151-Ex typically changes typical
±10% across the entire operating temperature range.
8.2

Other influencing variables

The PolyRex detector DOT1151-Ex is resistant to ambient light, air drafts and other
changes within the specified data.
The influence of air drafts with fast and large temperature fluctuations depends on the se-
lected parameter set.
9

Application

9.1

Compatibility

Fire detection system: S11 AlgoRex
Control unit:
Base:
CC11 (E3M171)
DB1151A