Verify that UPS installation has been carried out correctly and the UPS ground has been connected.
Select one of the following startup options:
Startup Option
Section
Normal mode
See paragraph
Battery mode
See paragraph
Bypass mode
See paragraph
UPS maintenance bypass
See paragraph
Bypass Power Module
Refer to the Eaton Bypass Power Module (BPM) User's Guide.
Parallel UPS
Refer to the Eaton 9155 Parallel UPS (8–15 kVA) User's Guide.
configuration
7 7 . . 2 2 . . 1 1 N N o o r r m m a a l l M M o o d d e e S S t t a a r r t t u u p p
1.
If you have an optional MBM/PDM, verify that the maintenance bypass switch is in the UPS position (see
Figure
52).
2.
If an optional isolation transformer is installed, switch the input circuit breaker to the ON position.
3.
Switch ON the utility power where the UPS is connected.
4.
Wait for the front panel LCD to illuminate.
The
indicator flashes.
5.
Switch all battery circuit breakers to the ON position.
The
indicator stops flashing.
6.
Press any button on the front panel display to activate the menu options.
7.
Press the
button on the front panel display and then press the
OFF menu.
8.
Press the
or
button to select the TURN UPS ON option; press and hold the
seconds, until the UPS stops beeping.
The
indicator illuminates. The UPS is now powering the load.
If the
indicator is flashing, check the UPS status from the front panel to view the active alarms.
Correct the alarms and restart if necessary.
7 7 . . 2 2 . . 2 2 S S t t a a r r t t i i n n g g t t h h e e U U P P S S o o n n B B a a t t t t e e r r y y
NOTE
Before using this feature, the UPS must have been powered by utility power at least
once.
To start the UPS on battery:
7.2.1 Normal Mode
Startup.
7.2.2 Starting the UPS on
Battery.
7.2.3 Internal Bypass
Startup.
7.2.4 Maintenance Bypass