Eaton 9155 UPS User Manual

Eaton 9155 UPS User Manual

Ups-mounted bypass switch
Hide thumbs Also See for 9155 UPS:

Advertisement

Quick Links

Eaton
® ®
9155 UPS
UPS-Mounted Bypass Switch
User's Guide
p/n: 164201644
Revision C0

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 9155 UPS

  • Page 1 Eaton ® ® 9155 UPS UPS-Mounted Bypass Switch User's Guide p/n: 164201644 Revision C0...
  • Page 2: Vcci Notice

    National Fire Protection Association, Inc. ERIFLEX and FLEXIBAR are registered trademark of Erico International Corporation. All other trademarks are property of their respective companies. ©Copyright 2006-2019 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3: Special Symbols

    Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA.
  • Page 5 4 4 W W a a r r r r a a n n t t y y ............................................................1 1 5 5 Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 6 Table of Contents Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 7 DANGER! Cet onduleur contient des TENSIONS MORTELLES. Toute opération d'entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L'UTILISATEUR ne se trouve dans l'onduleur. Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 8 100 amperios de protección contra sobrecorriente de circuito derivado, de acuerdo con el Código Eléctrico Nacional, ANSI/NFPA 70. • La protección contra sobrecorriente de salida y el conmutador de desconexión debe suministrarse por parte de terceros. Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 9 Both modules have a Make-Before-Break (MBB) maintenance bypass switch. NOTE If you are installing an optional isolation transformer with the MBM, refer to the Eaton 9155 UPS (8–15 kVA) User's Guide for installation instructions. 2 2 . . 1 1 M M B B M M / / P P D D M M S S e e t t u u p p If you purchased an optional MBM/PDM, attach the module to the UPS before any wiring installation.
  • Page 10: Ups-Mounted Bypass Switch Installation

    UPS electronics unit through an access slot. Figure 3. Installing the MBM or PDM (MBM Shown) UPS Electronics Unit MBM/PDM Wiring Access Cover Conduit Landing Plates Secure the sides of the module to the L-brackets using six screws (see Figure Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 11 W W i i r r i i n n g g t t h h e e M M B B M M / / P P D D M M The Eaton 9155 UPS has the following power connections: •...
  • Page 12 NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation of the Eaton 9155 UPS contain wiring to support the maximum capacity of the UPS cabinet. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure there is no power.
  • Page 13 16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements. Connect the factory-installed wiring from the maintenance bypass switch to the UPS terminal block (see Figure Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 14 10. Replace the wiring access cover on the UPS. 11. Replace the MBM/PDM wiring access cover and conduit landing plate. 12. Continue to “Stabilizing the Cabinet” in the Eaton 9155 UPS (8–15 kVA) User's Guide to complete the installation. Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 15 UPS-Mounted Bypass Switch Installation Figure 8. UPS with MBM Wiring Diagram Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 16 UPS-Mounted Bypass Switch Installation Figure 9. UPS with PDM Wiring Diagram Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 17 However, because BYPASS also disconnects AC input from the UPS, this is the appropriate position for UPS maintenance or repair. Figure 11 shows a UPS with a separate battery cabinet and a UPS-mounted bypass switch. Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 18: Maintenance Bypass Switch Operation

    Switch ON the utility power where the UPS is connected. The load is now powered by utility power. To transfer the load to the UPS, see paragraph 3.3 Transfer the Load from Maintenance Bypass to the UPS. Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 19: Control Panel Functions

    Th card. Alarm Indicator startup screen. The default is the Eaton logo and can be changed to the Mimic screen in the User Setting uminate. As the default or after 15 minutes of inactivity, the LCD displays the selectable in the User Settings menu.
  • Page 20 Maintenance Bypass Switch Operation Eaton 9155 User's Guide 164201644—Rev C0...
  • Page 21: Equipment Registration

    C C h h a a p p t t e e r r 4 4 W W a a r r r r a a n n t t y y For warranty information, please refer to the Resources link on our website, www.eaton.com/9155.
  • Page 22 164201644C0 164201644 C0...