Step 8: Test Water Detection - OneVue Sense E121 Installation Manual

Water leak sensor
Table of Contents

Advertisement

2.
Sensor settings (Go go Monitoring > Monitored Assets > select Monitored Asset > select sensor.
• Alarm Delay
By default, set to 0 (zero). A Wet reading automatically results in an Alarm state.
The Alarm Delay is the amount of time OneVue delays setting the sensor and Monitored Asset to an Alarm state
when in an Out of Range status. When it remains in an Out of Range for time period set in its Alarm Delay setting,
the sensor and its Monitored Asset are set to an Alarm state with a status of Out of Range, Past Alarm Delay.
By default set to 30 minutes, and can be set to immediate (0) or 1, 2, 8, 16, or 24 hours.
• Audio Alert (sensor gateway setting)
Primex sensors are equipped with an audio alert that is activated during a reading Alarm state (Out of Range,
Past Alarm Delay status). The audio alert is activated when a reading is out of range and the time period it has
been out of range has exceeded the time period set in its Alarm Delay.
By default audio alert is disabled.
• Logging Interval (sensor gateway setting)
The Logging Interval is how frequent a sensor logs a reading and stores it into its internal memory. All logged
readings are then sent to OneVue at the frequency set the sensor's Check-in Interval frequency.
By default set to 1 hour.
• Check-in Interval (sensor gateway setting)
The Check-in Interval is the frequency a sensor connects to the facility's network to sends its logged readings to
OneVue. Also, during each check-in, pending setting updates are downloaded to the sensor.
By default set to 8 hours.
• Unresponsive Timeout (sensor gateway setting)
The Unresponsive Timeout is the maximum amount of time a Primex device can go without a check-in to
OneVue. When this time limit is exceeded, the device is set to an Alarm state with an Unresponsive status.
By default set to 16 hours.

Step 8: Test water detection

Test triggering a Wet reading at the time of installation; H2O displayed on LCD screen and Wet reading is transmitted to
OneVue.
Detects water bridge across the two metal contacts located on the bottom side of the Water Detector. A change to the
voltage reading measurement detects a dry or wet condition. When water reaches both metal contacts, activates a
change to the voltage reading measurement that is then received by Water Leak Sensor.