Benning CM 9-1 Operating Manual page 19

Leakage current clamp
Table of Contents

Advertisement

Available languages

Available languages

TRUE RMS leakage current clamp according to EN 61557-13 for
-
measuring the leakage currents (differential current and protective con-
ductor current) in electrical systems and devices
-
AC/ DC voltage measurements
-
AC current measurements
-
resistance measurements
-
continuity tests
Table of contents
1. User instructions
2. Safety instructions
3. Scope of delivery
4. Device description
5. General information
6. Ambient conditions
7. Electrical specifications
8. Measuring with the BENNING CM 9-1
9. Maintenance
10. Technical data of measuring accessories
11. Environmental note
1. User instructions
This operating manual is intended for
-
skilled electricians and
-
electrotechnically trained personnel.
The BENNING CM 9-1 is intended for making measurements in dry environ-
ment. It must not be used in power circuits with a nominal voltage higher than
CAT IV 300 V or CAT III 600 V (More details in Section 6. "Ambient conditions").
The following symbols are used in this operating manual and on the BENNING
CM 9-1:
Application around and removal from HAZARDOUS LIVE conductors
is permitted.
Warning of electrical danger!
Indicates instructions which must be followed to avoid danger to per-
sons.
Attention! Must comply with documentation!
This symbol indicates that the information provided in the operating
manual must be complied with in order to avoid risks.
Measuring category III is applicable to testing and measuring circuits
CAT III
connected to the distribution circuit of the low-voltage mains installa-
tion of a building.
Measuring category IV is applicable to testing and measuring circuits
CAT IV
connected to the feed-in point of the low-voltage mains installation
of a building.
Do not use the device in external low-frequency magnetic fields with
more than 30 A/m.
This symbol on the BENNING CM 9-1 indicates that the BENNING
CM 9-1 is equipped with protective insulation (protection class II).
Please observe the operating manual!
This symbol appears on the display to indicate a discharged battery.
This symbol designates the „continuity test" field. The buzzer is in-
tended for acoustic result output.
(DC) Direct voltage
(AC) Alternating voltage or current
Ground (voltage against ground)
10/ 2019
Operating manual
BENNING CM 9-1
BENNING CM 9-1
10