Emerson Rosemount Oxymitter DR Reference Manual page 47

In-situ oxygen probe
Hide thumbs Also See for Rosemount Oxymitter DR:
Table of Contents

Advertisement

Reference Manual
00809-0100-4880
4. Replace with new EPROM.
5. Close electronics enclosure and power up system.
2.4.5
Set up World Class 3000 intelligent field transmitter
The Rosemount
voltage selection jumpers in the IFT or HPS, if used, are set properly.
IFT 3000 power supply board jumper configuration
WARNING
Always disconnect line voltage from intelligent field transmitter before changing jumpers.
Line voltage selection
100 Vac
120 Vac
220 Vac
240 Vac
Probe heater voltage selection
World Class probe (44 V)
218 probe (115 V)
World Class Direct Replacement probe (115 V)
or Rosemount Oxymitter Direct Replacement
probe (115 V)
CAUTION
If incorrect heater voltage is selected, damage to the probe may occur.
Always update the relevant labeling to reflect the select voltage.
Heater power supply (HPS 3000) jumper configuration
WARNING
Always disconnect line voltage from heater power supply and analog electronics (if used)
before changing jumpers.
Line voltage selection
100/120 Vac
220/240 Vac
(1)
100 Vac operation requires transformer part number 1M03961G02.
Rosemount Oxymitter DR
Oxymitter DR probe operates with a 115 Vac heater. Ensure that the
(1)
Jumper (install)
JM3, JM7, JM2
JM8, JM7, JM1
JM6, JM5, JM2
JM6, JM5, JM1
Jumper (install)
JM10
JM9
JM9
Jumper (install)
JM4, JM1
JM5
Install
October 2019
47