ROD4plus / ROD4-08plus Area Scanning Distance Sensor T E C H N I C A L D E S C R I P T I O N...
Page 2
Leuze electronic GmbH + Co. KG P.O. Box 1111, D- 73277 Owen / Teck Tel. +49(0) 7021/ 573-0, Fax +49(0)7021/ 573-199 info@leuze.de • www.leuze.com Sales and Service Germany Sales Region North Sales Region South Sales Region East Phone 07021/573-306 Phone 07021/573-307...
European standards and directives. Notice! The corresponding declaration of conformity can be requested from the manufacturer. The manufacturer of the product, Leuze electronic GmbH + Co. KG in D-73277 Owen/Teck, possesses a certified quality assurance system in accordance with ISO 9001. LISTED rotoScan ROD4...
Safety notices Safety notices Safety standards The rotoScan ROD4plus / rotoScan ROD4-08plus distance sensor (abbreviated as ROD4…plus in the following) has been developed, produced and tested subject to the appli- cable safety standards. It represents the state of the art.
• If the start disable/manual restart is provided, a test of all detection fields should be performed prior to release - there must not be any objects in the detection fields. rotoScan ROD4... Leuze electronic...
• Vapours, smoke, dust and all particles visible in the air could affect the measurement values and cause the semiconductor outputs to switch off. • Avoid large temperature fluctuations. Leuze electronic rotoScan ROD4...
Figure 2.1: Attachment of the stick-on label with warning notices Attention! Access and changes to the device , except where expressly described in this operating man- ual, are not authorised. rotoScan ROD4... Leuze electronic...
Mounting, commissioning and maintenance of the device may only be carried out by quali- fied personnel. Electrical work must be carried out by a certified electrician. Repair Repairs must only be carried out by the manufacturer or an authorised representative. Leuze electronic rotoScan ROD4...
Description Description Technical overview Designation Type Part No. rotoScan ROD4plus without heater 501 06481 with integrated heating, rotoScan ROD4-08plus 501 06480 dust-insensitive version Table 3.1: Device types The ROD4…plus is an optical, two-dimensional measuring distance sensor. It could also be referred to as an optical, area radar unit.
The ROD4…plus can detect objects with diameters greater than 20mm at a distance of up to 4.0m, even if the surface of the given object is dark. Larger objects are detected in the far detection field at a distance of up to 50m. Leuze electronic rotoScan ROD4...
One scan over the working range returns 529 measurement values (from angle -5.04° to angle +185.04° with 0.36° angular resolution). Thus, each individual measurement value corresponds to an angular segment of 0.36°. The measurement values are sequentially numbered from segment 0 (-5.04°) to segment 528 (+185.04°), see figure 3.2. rotoScan ROD4... Leuze electronic...
- Area configuration - Measurement data filtering: minimum and maximum values - Online commands • Four freely programmable near detection fields (up to maximum 30m) • Four freely programmable far detection fields (up to maximum 50m) Leuze electronic rotoScan ROD4...
The following examples can be considered typical areas of application for the ROD4…plus. 3.4.1 Object measurement: Gripping system Dimension and position measurement for gripping operations Figure 3.4: Application example - gripping system Gantry crane ROD4…plus for positioning a gantry crane Figure 3.5: Application example - gantry crane rotoScan ROD4... Leuze electronic...
Description Pallet measurement Dimension measurement in materials handling Figure 3.6: Application example - dimension measurement 3.4.2 Object detection Driverless transportation system ROD4…plus as the "eye" of a service robot Figure 3.7: Application example - service robot Leuze electronic rotoScan ROD4...
Overshoot and dimension detection of cars to prevent damage to the car Figure 3.8: Application example - automatic parking garage High-bay warehouse Overshoot detection for collision prevention with high-bay storage devices Figure 3.9: Application example - high-bay warehouse rotoScan ROD4... Leuze electronic...
Page 19
• Buffing protection (e.g. for telpher lines) • Overshoot detection (e.g. in fully automatic parking systems) • Detection / counting of persons • Room security / façade monitoring • Access control • Contour measurement • Packet measurement / volume measurement • etc. Leuze electronic rotoScan ROD4...
(a in figure 9.3). Mounting system BT ROD4…plus, see chapter 8.2.6. Notice! Under certain circumstances, a larger measurement inaccuracy may occur with strongly re- flective backgrounds (e.g. retro-reflectors). rotoScan ROD4... Leuze electronic...
Figure 5.1: Connecting the rotoScan ROD4…plus Attention! Should you not need one of the interfaces, close the respective connector with a blank plug. If a connector remains open, the ROD4…plus no longer has protection class IP 65. Leuze electronic rotoScan ROD4...
RS 232/RS 422 interface • Factory setting: Measurement data trans- M12 plug fer at 115kbit/s 8-pin • Configuration, measurement data trans- fer, diagnostics with RODplussoft Table 5.1: Connections of the ROD4…plus – Y1 to Y4 rotoScan ROD4... Leuze electronic...
Pin assignments for connection Y2 For an Ethernet connection, you should connect TX+ to TX+, TX- to TX-, RX+ to RX+ and RX- to RX-. The contact assignments on the Y2 M12-socket correspond to the PROFInet Leuze electronic rotoScan ROD4...
Connection M12 to RJ45 (1:1) 5.1.4 Connector assignments for connection Y3 (service) Signal Description Do not use! Data communication, transmission Data communication, ground Data communication, reception Do not use! Table 5.6: Pin assignments for connection Y3 rotoScan ROD4... Leuze electronic...
GND/shield cabinet side with PE) Selection RS 232/RS 422, RS 422 RS 232: leave PIN 6 open RS 422: bridge to PIN 5! Do not use! Do not use! Table 5.7: Pin assignments for connection Y4 Leuze electronic rotoScan ROD4...
• Both detection field pairs are active in this state! • Detection field pair 1 (Y1-E) is switched off if the voltage at pin Y1-E is removed. • Detection field pair 2 (Y1-G) is active in this state. rotoScan ROD4... Leuze electronic...
ROD4…plus switches over within the response time. Attention! If more than two detection field pairs are selected, the ROD4…plus reports a fault at output ALARM1 (Y1-R) and via the corresponding LED in the display field. Leuze electronic rotoScan ROD4...
"low". This means that alarm output "ALARM1" is also on "low" independent of its configu- ration. "ALARM2" (Y1-P) The "low" output state always signals warning and malfunction states, independent of how output "ALARM1" (Y1-R) is configured. rotoScan ROD4... Leuze electronic...
5.3.1 Y2 default settings The Ethernet interface is configured ex works as follows: • IP address: 192.168.60.3 • Subnet mask: 255.255.255.0 Notice! You can use RODplussoft to change the configuration of interface Y2. Leuze electronic rotoScan ROD4...
Y4 default settings The PC interface is configured ex works as follows: • Baud rate: 115.2kBd • Data bits: • Stop bits: • Parity: none Notice! Only the transmission rate of the interface can be changed using RODplussoft. rotoScan ROD4... Leuze electronic...
If the LED does not illuminate, there are still objects located within the near detection field. In this case, change the location of the button and perform the test again. Leuze electronic rotoScan ROD4...
(make before break) and are operated directly at the two semiconductor outputs Fn1 (Y1-N) and Fn2 (Y1-O). The two semiconductor outputs possess an internal electronic current limit and are protected in the event of errors by fuse SI 2. rotoScan ROD4... Leuze electronic...
"WA". The relays K1 and K2 used here have overlapping contacts (make before break) and are operated directly at the two secure semiconductor outputs Fn1 (Y1-N) and Fn2 (Y1-O). Leuze electronic rotoScan ROD4...
RODplussoft and RODsoft. RODsoft is called up via RODplussoft. The use of interface Y3 for device configuration is a prerequisite for using RODsoft. Notice! The programs are described in the manuals, which can likewise be found on the supplied CD as PDF files. rotoScan ROD4... Leuze electronic...
ROD4…plus is performed during normal operation. Upon detection of an obstacle, a new measurement segment can be defined around the obstacle. Measurement is then performed with the maximum possible accuracy within this area. Leuze electronic rotoScan ROD4...
Before commissioning the device, you must adjust the device parameters and the detection fields for your application. To do this, configure the ROD4…plus using the RODsoft software user manual so that the detection fields are optimised for the monitoring task. rotoScan ROD4... Leuze electronic...
Once the device is installed, the required device parameters set and the detection fields defined, the ROD4…plus can be put into operation. After you have switched on the voltage supply of the ROD4…plus, illumination of the red LED on the interface box indicates the operational readiness of the ROD4…plus. Leuze electronic rotoScan ROD4...
Do not use solvents or cleaning agents containing acetone. Use of improper cleaning agents can damage the optical window. If window monitoring continues to report a soiled cover even after cleaning, it must be replaced with a new front cover. rotoScan ROD4... Leuze electronic...
8.2.2 Pin assignments KB-ROD4plus… Signal Core colour PIN on Sub-D socket connector brown white blue black grey 8.2.3 Pin assignments KB ET-…-SA-RJ45 (cross-over cable) M12-Stecker Signal Core colour RJ45 yellow orange white blue rotoScan ROD4... Leuze electronic...
Pin assignments KB ET-…-SA Signal Core colour connector yellow orange white blue 8.2.5 Pin assignments K-D M12A-8P-… M12 socket Signal Core colour Tx+/TxD white brown green Rx+ / RxD yellow GND/shield grey RS 422 pink blue Leuze electronic rotoScan ROD4...
With the aid of the BT-ROD4 mounting system, pitches of maximum 8° downward or upward are possible. In addition, the mounting kit allows lateral inclinations of up to ±4°. Lateral view Scanner mounting surface Part overview All dimensions in mm Figure 8.1: Dimensioned drawing BT ROD4…plus rotoScan ROD4... Leuze electronic...
4 (selectable via switching inputs) Output one PNP transistor output, max. 100mA Particularly in the far range, the ROD4-08plus only detects large objects and objects with high diffuse reflection Table 9.2: Technical data - detection fields Leuze electronic rotoScan ROD4...
1 stop bit With RODplussoft, all three interfaces can be used for configuration. Measurement data can be transferred either via Y2 or Y4. RODsoft can only communicate with the ROD4…plus via interface Y3. rotoScan ROD4... Leuze electronic...
Distance [m] Diffuse reflection in % for the ROD4-08plus 10000 Reflector 1000 White plaster, writing paper Grey cardboard (18%) Black cord Distance [m] Figure 9.1: Object size/diffuse reflection as a function of distance for the ROD4plus rotoScan ROD4... Leuze electronic...
Technical data Beam dimensions in mm Light spot height Y Light spot width X Distance [m] Figure 9.2: Typical beam dimensions with the ROD4…plus Leuze electronic rotoScan ROD4...
Interference rejection test impulse 1, 2, 3a, 3b and 5 (no application for vehi- cles with combustion motors) Rotating mirror drive brushless DC motor Rotating mirror bearings maintenance-free ball bearing Table 9.6: Technical data - environmental data rotoScan ROD4... Leuze electronic...
Technical data Dimensioned drawingROD4…plus Zero point for measuring Scanning plane All dimensions in mm Figure 9.3: Dimensioned drawingROD4…plus Leuze electronic rotoScan ROD4...
IP 65. When in a voltage-free state, the LEDs are hidden from view by this cover. Figure 10.1:Ethernet status indicator LED Colour Function / Meaning Ethernet system ready Ethernet connection present Ethernet data transmission active rotoScan ROD4... Leuze electronic...
Near detection field is occupied, Fn outputs are switched off green Near detection field is free, Fn outputs are active • Slowly flashing (SF) at approx. 1Hz: warning message yellow • Flashing fast (FF) at approx. 4Hz: error message • Continuous light (CL): restart-disable locked Leuze electronic rotoScan ROD4...
You can only call up this list with the RODsoft software. On the toolbar, click or select System data Load diagnostic data from scanner on the menu bar. The error messages from the last 8 events are documented. This first memory slot always contains the most recent error message. rotoScan ROD4... Leuze electronic...
Switching output Fn1/Fn2 does not switch 1110 Test of the switching outputs Short-circuit test of the switching out- A switching output Fn1/Fn2 is short 1111 puts circuited with ground Table 10.2: ROD4…plus - Diagnostic codes and causes Leuze electronic rotoScan ROD4...
Page 54
2201 Field monitoring the motor or switching off of the watchdog; internal fuse defective Error occurred during ROD4…plus start- 2302 Control of software execution up, secondary error Table 10.2: ROD4…plus - Diagnostic codes and causes rotoScan ROD4... Leuze electronic...
Page 55
No detection field activated during start-up 2802 detection field switching of the ROD4…plus Monitoring of the access authorisation Confirmed single password has been 3016 with one-time password entered incorrectly Table 10.2: ROD4…plus - Diagnostic codes and causes Leuze electronic rotoScan ROD4...
Working range The working range of the ROD4…plus (190° - from -5.04° to 185.04°) is divided into 0.36° angular segments (corresponds to 529 measurement values). See "Working range and angular resolution" on page 12. rotoScan ROD4... Leuze electronic...