Control modules with analog outputs
Hide thumbs Also See for System 450 Series:

Advertisement

Quick Links

Application
Important: Use this System 450™ Series Control
Module with Analog Outputs only as an operating
control. Where failure or malfunction of the System
450 could lead to personal injury or property damage
to the controlled equipment or other property,
additional precautions must be designed into the
control system. Incorporate and maintain other
devices, such as supervisory or alarm systems or
safety or limit controls, intended to warn of or
protect against failure or malfunction of the System
450 Module.
Important: Utiliser ce System 450 Series Control
Module with Analog Outputs uniquement en tant
que dispositif de contrôle de fonctionnement.
Lorsqu'une défaillance ou un dysfonctionnement
du System 450 risque de provoquer des blessures
ou d'endommager l'équipement contrôlé ou un
autre équipement, la conception du système de
contrôle doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que
des systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du System 450
Module.
System 450 is a family of modular, digital electronic
controls that you can easily assemble and set up to
provide reliable temperature, pressure, and humidity
control for a wide variety of HVACR and commercial and
industrial process applications.
You can use the System 450 control modules to configure
custom application-specific control systems with up
to three input sensors and 10 (relay, analog, or both)
outputs, including control systems that can monitor and
control temperature, pressure, and humidity applications
simultaneously.
You can easily install and quickly configure a stand-
alone System 450 control module and sensor in the field
as a replacement control for almost any temperature,
pressure, and humidity control.
C450CPN-4 and C450CQN-4 models are analog output
control modules with LCD and a four-button touchpad UI
for setting up a System 450 control system. C450CPN-4
models provide one self-selecting analog output, and
C450CQN-4 models provide two self-selecting analog
outputs.
Refer to the System 450 Series Modular Control Systems with
Standard Control Modules Technical Bulletin (LIT-12011459)
for more detailed information on designing, installing,
setting up, and troubleshooting System 450 Series control
systems.
System 450 Series Control Modules with Analog
Outputs Installation Guide
Installation
Figure 1: System 450 module dimensions, mm (in.)
Location considerations
Observe the following System 450 location guidelines:
• Ensure that the mounting surface can support the
module assembly, mounting hardware, and any user-
supplied panel or enclosure.
• Mount the modules upright and plugged together in a
horizontal row where possible. See Figure 3. It is best
practice to mount the module with a DIN rail.
• Mount modules on flat, even surfaces.
• Allow sufficient space for wires and connections.
• Mount the modules in locations free of corrosive
vapors. Observe the ambient operating conditions
listed in the
System 450 Series Control Modules with
Analog Outputs technical
• Do not mount the modules on surfaces that are prone
to vibration or in locations where radio frequency or
electromagnetic emissions may cause interference.
• Do not install the modules in airtight enclosures.
• Do not install heat-generating devices in an enclosure
with the modules that may cause the temperature to
exceed the ambient operating limit.
24-7664-3191 Rev. C
2021-01-14
specifications.
C450CPN, C450CQN

Advertisement

loading

Summary of Contents for Penn System 450 Series

  • Page 1 • Do not install heat-generating devices in an enclosure outputs. with the modules that may cause the temperature to Refer to the System 450 Series Modular Control Systems with exceed the ambient operating limit. Standard Control Modules Technical Bulletin (LIT-12011459)
  • Page 2 V and COM terminals on the control module), but you cannot connect to both power sources simultaneously. Connecting a control module to both internal and external power sources can damage the modules and void any warranty. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 3 2.5 mm terminal; either 0–10 VDC or 4–20 mA. 28 AWG to 14 AWG Provides a low voltage circuit Common (C) path for the analog outputs (AO1 and AO2) System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 4: Setup And Adjustments

    If the sensors are set up in the outputs, which requires setting up the outputs UI but not connected, the LCD displays again. an SNF Sensor Failure. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 5 Johnson Controls firmware. when the sensed property is at Setpoint. The control ramp icon displayed is Figure 5: Startup screen determined by the output's SP, EP, OSP, and OEP setup values. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 6 Setup Start Access the System 450 Setup Start screens from the screens. Main screen. See Viewing the Startup, Main, and System To access the System 450 setup screens: System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 7 0 to 500 90 to 500 P499RAP-105C P499RAP-105K P499RCP-105C P499RCP-105K P599RAPS105C P599RAPS105K P599RCPS105C P599RAPS105K P 750 PSI (Pressure/psi) 0 to 750 150 to 750 P499RAP-107C P499RAP-107K P499RCP-107C P499RCP-107K P599RAPS107C P599RAPS107K P599RCPS107C P599RCPS107K System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 8 System 450 Differential Control feature. Refer to the System 450 Series Modular Controls Product Bulletin (LIT-12011458), Catalog Page (LIT-1900549), or the System 450 Series Controls Systems Technical Bulletin (LIT-12011459) for additional ordering information for System 450 compatible sensors and transducers.
  • Page 9 Sensor Type °C enables an -4.5 -9.5 offset of +/- 2.5°C in 0.5 degree increments. -5.0 -10.0 Note: The temperature offset changes the displayed temperature value by the selected offset value. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 10: Differential Control

    (dON, dOFF, dSP, and dEP). When a Differential Control sensor (Sn-d) is set up, the displayed differential sensor value is a calculated variable value: (Sn-d) = (Sn-1) – (Sn-2). System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 11 In the Sensor Selection screen, press Up or Down to select the sensor that the output references: System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 12 If you select and save a sensor set up as a binary input in Step 2, the ON Delay (ONd) screen appears. Go to Step 5. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 13 If you select and save a sensor set up as a binary input in Step 2, the ON Delay (ONd) screen appears. Go to Step 5. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 14 (Sn-1, Sn-2, or Sn-3) or a High Input Signal Selection sensor (HI-2 or HI-3). Note: The differential sensor, Sn-d, is used to set up analog and relay outputs for Differential Control. See Differential control for more information. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 15 Signal Strength at End Point (OEP). The LCD displays different Control Ramp icons for the four control actions. Table 6 shows the four Control Ramp icons and the associated analog output setup value relationships. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 16 Failure to observe and adjust an analog output set up to use the I-C, UP-R, or bNd features can result in unexpected behavior and out of range conditions in the affected process loops. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 17 In the following figure, the top screen example shows a Setpoint value of 225 (psi) selected for Output 3. The bottom screen example shows a dSP value of 30 (psi) selected for Output 3. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 18 Proportional plus integral control can drive the load closer to Setpoint than proportional only control. Press Next to save your selection and go to the Output Update Rate Selection screen. System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 19 To change the sensor the output references, is within the selected Output Signal Deadband, press Up or Down to select the new sensor the output signal strength is not updated System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 20 Figure 40: Backlight Setup Start screen In the Backlight Setup Start screen, press Next to go to the Edit Backlight Low Level screen. Figure 37: Backlight Setup Start screen System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 21 System 450 menu flow examples Figure 41: System 450 status screens, setup screens, and menu flow example System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 22 Humidity: Up to 95% RH Non-condensing; Maximum Dew Point 29°C (85°F) Input signal 0–5 VDC; 1,035 ohms at 25 ° C (77 ° F) for an A99 PTC Temperature Sensor System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 23: North American Emissions Compliance

    Software terms Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services applicable to this product, if any, is System 450 Series Control Modules with Analog Outputs Installation Guide...
  • Page 24 Single point of contact APAC Europe NA/SA JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS C/O CONTROLS PRODUCT WESTENDHOF 3 507 E MICHIGAN ST MANAGEMENT 45143 ESSEN MILWAUKEE WI 53202 NO. 32 CHANGJIJANG RD NEW GERMANY DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA ©...