PENN | TC3B23 | Installation Guide Rev. B | Part No. 24-7664-03574 | Page 1 of 2 | 07 April 2020
TC3B23
E
ENGLISH
-
Controller for low temperature units.
-
Power supply for TC3B23N5V: 115 VAC.
-
Power supply for TC3B23N7V: 230 VAC.
-
Cabinet probe and auxiliary probe (NTC).
-
Door switch/multi-purpose input.
-
Cooling or heating operation.
1
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
-
The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
-
Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
-
In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
-
Power supply for TC3B23N5V: 115 VAC.
-
Power supply for TC3B23N7V: 230 VAC.
PRECAUTIONS FOR ELECTRICAL CONNECTION
If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
-
0.5 N•m (4 in. lb).
-
If the device was moved from a cold to a warm place, the humidity may have caused
condensation to form inside. Wait about an hour before switching on the power.
Make sure that the supply voltage, electrical frequency and power are within the set
-
limits. See the section TECHNICAL SPECIFICATIONS.
-
Disconnect the power supply before doing any type of maintenance.
Do not use the device as safety device.
-
For repairs and for further information, contact the PENN sales network.
-
3
FIRST-TIME
1.
Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2.
Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3.
Configure the device as shown in Table 6.1 in the section SETTINGS.
Recommended configuration parameters for first-time use.
PAR.
DEF.
PARAMETER
SP
0.0
setpoint
P2
0
temperature unit of measurement
d1
0
defrost type
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
6.
Power up the device.
4
USER INTERFACE AND MAIN FUNCTIONS
4.1
Switching the device on/off
1.
If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
Basic controller for refrigerated cabinets,
LED
ON
compressor on
defrost or pre-dripping
active
evaporator fan on
- if device on, energy
saving active
- if
consumption active
view temperature
°C/°F
device off
If 30 s have elapsed without the keys being pressed, the display will show the "Loc" label and
the keypad will lock automatically.
4.2
Unlock keypad
Touch any key for 1 s: the display will show the label "UnL".
4.3
Set the setpoint
Check that the keypad is not locked.
1.
2.
3.
4.4
Activate manual defrost (if r5 = 0, default)
Check that the keypad is not locked.
1.
If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
5
ADDITIONAL FUNCTIONS
5.1
View/delete compressor functioning hours
Check that the keypad is not locked.
1.
2.
LAB.
CH
rCH
3.
4.
5.
6.
5.2
View the temperature detected by the probes
Check that the keypad is not locked.
1.
2.
LAB.
Pb1
Pb2
3.
4.
6
SETTINGS
6.1
Setting configuration parameters
1.
2.
3.
4.
5.
6.
7.
8.
9.
MIN... MAX.
r1... r2
6.2
Restore the factory settings (default) and store customized settings as default
0 = °C
1 = °F
0 = electric
1 = hot gas
Important
2 = compressor stopped
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- When you store customized settings, you overwrite the default.
1.
2.
3.
VAL.
149
161
4.
5.
6.
7.
8.
Interrupt the power supply to the device.
9.
with energy-saving strategies
OFF
FLASHING
compressor off
- compressor protection active
- setpoint setting active
-
- defrost delay active
- dripping active
evaporator fan off
evaporator fan stop active
-
-
device
off,
low
-
-
device on
device on/off active
Touch the SET key.
Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default "-40... 50")
Touch the SET key (or do not operate for 15 s).
Touch the UP key for 2 s.
Touch the DOWN key for 4 s.
Touch the UP or DOWN key within 15 s to select a label.
DESCRIPTION
view compressor functioning hours (hundreds)
delete compressor functioning hours
Touch the SET key.
Touch the UP or DOWN key to set "149" (when label "rCH" is se-
lected).
Touch the SET key.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
Touch the DOWN key for 4 s.
Touch the UP or DOWN key within 15 s to select a label.
DESCRIPTION
cabinet temperature
auxiliary temperature
Touch the SET key.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
Touch the SET key for 4 s: the display will show the label "PA".
Touch the SET key.
Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault "-19").
Touch the SET key (or do not operate for 15 s): the display will
show the label "SP".
Touch the UP or DOWN key to select a parameter.
Touch the SET key.
Touch the UP or DOWN key within 15 s to set the value.
Touch the SET key (or do not operate for 15 s).
Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
Touch the SET key for 4 s: the display will show the label "PA".
Touch the SET key.
Touch the UP or DOWN key within 15 s to set the value.
DESCRIPTION
value to restore the factory settings (default)
value to store customized settings as default
Touch the SET key (or do not operate for 15 s): the display will
show the label "dEF" (when value "149" is set) or the label
"MAP" (when value "161" is set).
Touch the SET key.
Touch the UP or DOWN key within 15 s to set "4".
Touch the SET key (or do not operate for 15 s): the display will
show for 4 s "- - -" flashing, then the device will exit the proce-
dure.
Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.
7
CONFIGURATION PARAMETERS
N.
PAR.
DEF.
SETPOINT
1
SP
0.0
setpoint
N.
PAR.
DEF.
ANALOG INPUTS
2
CA1
0.0
cabinet probe offset
3
CA2
0.0
auxiliary probe offset
4
P0
1
probe type
5
P1
1
enable °C decimal point
6
P2
0
temperature
unit
measurement
7
P4
1
auxiliary probe function
8
P5
0
value displayed
9
P8
5
display refresh time
N.
PAR.
DEF.
CONTROL
10
r0
2.0
setpoint differential
11
r1
-40
minimum setpoint
12
r2
50.0
maximum setpoint
13
r4
0.0
setpoint offset in energy saving
14
r5
0
cooling or heating operation
15
r12
1
position of the r0 differential
N.
PAR.
DEF.
COMPRESSOR
16
C0
0
compressor on delay after pow-
er-on
17
C2
3
compressor off minimum time
18
C3
0
compressor on minimum time
19
C4
0
compressor off time during cabi-
net probe alarm
20
C5
10
compressor on time during cabi-
net probe alarm
21
C6
80.0
threshold
for
high
condenser
temperature warning
22
C7
90.0
threshold
for
high
condenser
temperature alarm
high
condenser
temperature
23
C8
1
alarm delay
N.
PAR.
DEF.
DEFROST (if r5 = 0)
24
d0
8
automatic defrost interval
25
d1
0
defrost type
26
d2
2.0
threshold for defrost end
27
d3
30
defrost duration
28
d4
0
enable defrost at power-on
29
d5
0
defrost delay after power-on
30
d6
1
value displayed during defrost
31
d7
2
dripping time
32
d8
0
defrost interval counting mode
33
d9
0.0
evaporation threshold for auto-
matic defrost interval counting
34
d11
0
enable defrost timeout alarm
35
d15
0
compressor on consecutive time
for hot gas defrost
36
d18
40
adaptive defrost interval
37
d19
3.0
threshold for adaptive defrost
(relative to optimal evaporation
temperature)
38
d20
180
compressor on consecutive time
for defrost
39
d22
2.0
evaporation threshold for adap-
tive
defrost
interval
counting
(relative to optimal evaporation
temperature)
N.
PAR.
DEF.
ALARMS
40
A1
10.0
threshold for low temperature
alarm (relative to setpoint)
41
A4
10.0
threshold for high temperature
alarm (relative to setpoint)
42
A6
12
high temperature alarm delay af-
ter power-on
43
A7
15
high/low temperature alarms de-
lay
44
A8
15
high temperature alarm delay af-
ter defrost
45
A9
15
high temperature alarm delay af-
ter door closing
46
A11
2.0
high/low temperature alarms re-
set differential
N.
PAR.
DEF.
FANS
47
F0
3
evaporator
fan
mode
during
normal operation
48
F1
-1.0
threshold for evaporator fan op-
eration
49
F2
0
evaporator fan mode during de-
frost and dripping
50
F3
2
evaporator
fan
off
maximum
time
51
F4
30
evaporator fan off time during
energy saving
52
F5
30
evaporator fan on time during
energy saving
MIN... MAX.
r1... r2
MIN... MAX.
-25... 25 °F/°C
-25... 25 °F/°C
0 = n/a
1 = NTC
0 = no
1 = yes
of
0 = °C
1 = °F
0 = disabled
1 = evaporator
probe
(de-
frost + fan)
2 = evaporator probe (fan)
3 = condenser probe
0 = cabinet temperature
1 = setpoint
2 = auxiliary temperature
0... 250 s : 10
MIN... MAX.
1... 15 °F/°C
-99 °F/°C... r2
r1... 199 °F/°C
0... 99 °F/°C
0 = cooling
1 = heating
0 = asymmetric
1 = symmetric
MIN... MAX.
0... 240 min
0... 240 min
0... 240 s
0... 240 min
0... 240 min
0... 199 °F/°C
differential = 4 °F/2 °C
0... 199 °F/°C
0... 15 min
MIN... MAX.
0... 99 h
0 = only manual
if d8 = 3, maximum interval
0 = electric
1 = hot gas
2 = compressor stopped
-99... 99 °F/°C
0... 99 min
if P3 = 1, maximum duration
0 = no
1 = yes
0... 99 min
0 = cabinet temperature
1 = display locked
2 = dEF label
0... 15 min
0 = device on hours
1 = compressor on hours
2 = hours evaporator tem-
perature < d9
3 = adaptive
-99... 99 °F/°C
0 = no
1 = yes
0... 99 min
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
0... 40 °F/°C
optimal evaporation tempera-
ture - d19
0... 999 min
0 = disabled
0... 19 °F/°C
optimal evaporation tempera-
ture + d22
MIN... MAX.
0... 99 °F/°C
SP - A1
0 = disabled
0... 99 °F/°C
SP + A4
0 = disabled
0... 99 min x 10
0... 240 min
0... 240 min
0... 240 min
1... 15 °F/°C
MIN... MAX.
0 = off
1 = on
2 = on if compressor on
3 = thermoregulated
(with
F1)
4 = thermoregulated
(with
F1) if compressor on
-99... 99 °F/°C
differential = 2 °F/1 °C
0 = off
1 = on
2 = according to F0
0... 15 min
0... 240 s x 10
0... 240 s x 10

Advertisement

loading

Summary of Contents for Penn TC3B23

  • Page 1 PENN | TC3B23 | Installation Guide Rev. B | Part No. 24-7664-03574 | Page 1 of 2 | 07 April 2020 Basic controller for refrigerated cabinets, TC3B23 with energy-saving strategies FLASHING CONFIGURATION PARAMETERS compressor on compressor off - compressor protection active - setpoint setting active PAR.