Operating Conditions; Operating And Display Elements; Installation And Operation - Rittal CMC III Installation Manual And Short User's Manual

Table of Contents

Advertisement

Available languages

Available languages

3.4

Operating conditions

The power unit may only be operated under the following operating conditions:
Temperature operational range:
Humidity operational range:
Degree of protection:
4
Assembly
4.1
Assembly instructions
The assembly of the power unit is made as shown in fig. 2.
5

Installation and operation

5.1

Operating and display elements

The operating and display elements are shown in fig. 3.
Key for fig. 3
1
"C" key to acknowledge messages
2
Multi-LED for the status display
3
C14 supply voltage input, 100-230 V, 10 A, 50/60 Hz
4
C13 supply voltage output, 100-230 V, 50/60 Hz, max. 10 A in total with item 5
5
C13 supply voltage output, 100-230 V, 50/60 Hz, max. 10 A in total with item 4
6
CAN bus connection, 24 V
7
CAN bus connection, 24 V
5.2
Installation
Note:
The unit is free from power only after all power sources have been disconnected!
Connect an external consumer, e. g. a fan, to one of the two outputs for the power supply with an
appropriate cable (fig. 3, item 4, 5).
Select an appropriate country-specific connection cable for the power unit.
– PE plug and IEC connector connection cable (DK 7200.210)
– CMC IEC extension cable (DK 7200.215)
Insert the cable in the inlet of the power supply of the power unit and to the mains supply (fig. 3,
item 3).
Connect the power unit with a CAN bus connection cable to the CMC III PU or to the neighbouring
elements on the CAN bus (fig. 3, item 6, 7).
Display of the status change:
– The two green and the two red CAN bus LEDs on the CAN bus connection flash.
– The multi-LED of the Processing Unit flashes continually in the green – orange – red sequence.
– The multi-LED of the power unit flashes blue continuously.
Press the "C" key on the CMC III PU (a first audio signal is issued) and keep it pressed for approx.
3 seconds until a second audio signal is issued.
Display of the status change on the CAN bus LEDs:
– Green LEDs light continuously: CAN bus status "OK".
– Red LEDs light continuously: CAN bus status faulty.
Rittal CMC III Power Unit
Product description, Assembly, Installation and operation
+0°C...+55°C
5%...95% relative humidity, non-condensing
IP 30 in accordance with IEC 60 529
EN
7