normal operation, or if 004 is entered it will be shown as 4
during normal operation.
22. When the table has been entered, scroll through the table
values to verify the values.
23. If it is confusing to see existing volume calibration values
during table entry, you can erase the entire table by entering
all zeros in the linear calibration menu. This will put a single
"0" throughout the table.
24. EXIT MENU: To exit the programming mode, press ↑↑ FAST
UP until the exit menu is accessed, the display will show "CAL
donE". Press ENTER, "Prog donE" will be shown momentarily
and the gauge will return to normal operation. The software
release number is shown in this menu as well, for example
"rEL 3.11".
25. If a menu is left without pressing ENTER, any change to that
menu item will NOT be stored. If no button is pressed for 3
minutes then the gauge will exit programming mode and any
changes which have not been stored will be ignored.
900D4S Manual
Page 17

Hide quick links: