code menu will be accessed, the display will show "USEr
CodE XXXX XX", which is the existing user code.
4. Press the number buttons to enter the new six digit code,
the existing code will disappear from the appropriate display
and the new value will be shown. If exactly six digits are not
entered, then "Err" is shown momentarily and the previous
code reappears. If the number of digits is correct, then "Stor"
will be shown momentarily and the new code will be stored.
5. COPY MENU:
DOWN until the display shows "COPY". This allows remote
copying or programming by releasing control of the memory
so that the 900M remote programmer can access it.
6. Follow the directions for the remote programmer to perform
the desired functions. The gauge will stay in this mode for
about 3 minutes, and will automatically return to normal
operation if no button is pressed. If more time is needed
then press any number button before the 3 minutes is up to
reset the timer.
7. OFFSET MENU: The display must be connected to the sender
bar in order to set the offset. To access the offset menu, press
↑↑ FAST UP or ↓↓ FAST DOWN until the top left display shows
"OFFS". The top right display will show "XXX.X" which is the
fluid level in inches using the existing offset programmed into
the display, and the lower displays will show the number of
inches the bar output is changed to obtain the proper fluid
level (this number can be positive or negative). This bottom
number is for reference only; it is never shown during normal
operation. If the top right display shows "tohi" then the fluid
level has been set to over 960 inches, which is taller than the
tallest possible sender bar.
8. Determine where to set the offset. If the tank is empty,
measure from the bottom of the tank to the middle of the
vertical part of the float (for interface displays measure to
the top float, making sure that there is at least two inches
between the floats). If the tank has fluid in it manually gauge
the fluid level (top fluid level for interface displays). Set the
top left display inch reading to match this value using the ↑
UP or ↓ DOWN buttons, or to quickly get close to a desired
value, there are three speed buttons: 0 resets the offset to
zero, 1 decreases the offset by 10 inches, and 4 increases the
offset by 10 inches.
9. The volume calibration (barrel) displays, the 4-20mA/1-5V
outputs, and the alarms will all track with the inch reading, so
it is only required to set the offset once using the inch reading
for the float.
Page 14
To access the copy menu, press ↓↓ FAST
900D4S Manual