CRIMPING/TIGHTENING OF THE CONTACT
A
Compression type contacts (Type TBC-X)
adhesive
tape
1 For aluminium conductors : before installing the conductor contact, wire brush the conductor.
2 Fit the contact on to the conductor.
3 Position the crimp contact taking care that the contact hole aligns with the bushing hole.
4 Prior to crimping, distance « Z » must be between 225 and 230 mm.
5 Crimp the contact. Please refer to the crimp chart for crimp sequence.
6 After crimping distance « Z » must be between 225 and 235 mm.
If necessary, adjust the position of the cable reducer until distance « Z » is within the tolerance range.
Using adhesive tape, secure the cable reducer.
7 Remove any burrs left after crimping and wipe-off excess inhibitor.