11.4.6 Over-current of the compressor
Outdoor diplay
Method of
 
malfunction detection
 
Malfunction detection
conditions
 
 
Supposed causes
Troubleshooting
 
Electrify the machine again and turn it on
with the remote controller, If malfunctions
are reported before or upon the compressor
being started up,
The compressor is started normally, but
malfunctions are reported after it has
run for some time. Check the power
supply is too low or too high
the system may have been over or under charged
with gas, which can be judged through the
pressure of the measuring system.
LED1 flash 3 or 24 or 25 times  
he current of the compressor is too high  
when the IPM Module is damaged or the compressor is damaged.
voltage is too low or too high
■Faulty IPM Module
■ Faulty compressor
■Faulty power supply
* Caution
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred..
NO
NO
NO
.
Yes
Yes
318
Installations
power supply
IPM Module is damaged and
needs replacing.
Repair the power supply