2.2.7 Control for discontinuous operation

After the unit starts up in cooling/heating mode, in 5 minutes, the compressor run/stop will not be controlled by
the room temp., but after changing the set temp., if compressor stop condition can be met, the system will stop
compressor immediately.

2.2.7 Anti-cold air control

In heating mode, after compressor startup, the system will control indoor fan motor according to indoor coil
temperature. Detailed operation is as below:
Note:
1) The data in the parentheses is the control point when Tao>10oC;
2) Indoor unit will send "pre-heat" signal to wired controller in anti-cold air period.

2.2.8. Fan motor control in defrosting

A. On receiving outdoor defrosting signal, indoor unit will stop after blowing remaining heat at slow speed for 20
seconds.
B. In defrosting period, indoor fan motor stops running.
C. Defrosting is over, and indoor motor will run as anti-cold air state.
2.2.9 Blowing remaining heat operation
When the unit shuts off in heating mode or the thermostat is OFF, indoor motor will stop running after running at
low speed for 30 seconds.

2.2.10 Swing motor control

Indoor unit will control the swing motor according to the swing signal from the wired controller.
Full OFF 54 º
Tc2(℃)
30(32)
set speed
26(30)
low speed
22(26)
off
20(20)
Super Match
54°
Swing range
Standard position in
HEAT, COOL mode