8.3 Basic parameters
On the next pages you will find the list of parameters that are essential for the commissioning of the
frequency converter. You will find more details of these and other special parameters in the Multi-
Control Application manual.
Note! If you wish to edit the special parameters, you must set the value of
Column explanations:
Code
= Location indication on the keypad; Shows the operator the present param. number
Parameter
= Name of parameter
Min
= Minimum value of parameter
Max
= Maximum value of parameter
Unit
= Unit of parameter value; Given if available
Default
= Value preset by factory
Cust
= Customer's own setting
ID
= ID number of the parameter (used with PC tools)
On the parameter code: parameter value can only be changed after the FC has been
=
stopped
Monitoring values (Control keypad: menu M1)
8.3.1
The monitoring values are the actual values of parameters and signals as well as statuses and measurements.
Monitoring values cannot be edited. See Chapter 7.3.1 for more information.
Code
V1.1
Output frequency
V1.2
Frequency reference
V1.3
Motor speed
V1.4
Motor current
V1.5
Motor torque
V1.6
Motor power
V1.7
Motor voltage
V1.8
DC-link voltage
V1.9
Unit temperature
V1.10
Analogue input 1
V1.11
Analogue input 2
V1.12
Analogue output current
V1.13
Analogue output current 1, expander board
V1.14
Analogue output current 2, expander board
V1.15
DIN1, DIN2, DIN3
V1.16
DIE1, DIE2, DIE3
V1.17
RO1
V1.18
ROE1, ROE2, ROE3
V1.19
DOE 1
V1.20
PID Reference
V1.21
PID Actual value
V1.22
PID Error value
V1.23
PID Output
Table 8-1. Monitoring values
Vacon Oyj
Commissioning
.
Parameter
Telephone:
24-hour support:
Unit
ID
Hz
1
Frequency to the motor
Hz
25
rpm
2
Calculated motor speed
A
3
Measured motor current
%
4
Calculated actual torque/nominal torque of the unit
%
5
Calculated actual power/nominal power of the unit
V
6
Calculated motor voltage
V
7
Measured DC-link voltage
ºC
8
Heat sink temperature
V
13
AI1
mA
14
AI2
mA
26
AO1
mA
31
mA
32
15
Digital input statuses
33
I/O expander board: Digital input statuses
34
Relay output 1 status
35
I/O exp. board: Relay output statuses
36
I/O exp. board: Digital output 1 status
%
20
In percent of the maximum frequency
%
21
In percent of the maximum actual value
%
22
In percent of the maximum error value
%
23
In percent of the maximum output value