Service menu
10.4
Set voltage limits
The "Set voltage limit" menu is used to set the monitoring limits for overvoltage and
undervoltage.
10.4.1 Set Ua max. 12V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
overvoltage where output voltage is 12 V.
Default setting: 16.0V
10.4.2 Set Ua min. 12V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
undervoltage where output voltage is 12V.
Default setting: 7.0V
10.4.3 Set Ua max. 24V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
overvoltage where output voltage is 24V.
Default setting: 32.0V
10.4.4 Set Ua min. 24V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
undervoltage where output voltage is 24V.
Default setting: 14.0V Setting range: 14.0V to 20.0V
2280073 Rev.1
Setting range: 9.0V to 16.0V
Setting range: 7.0V to 10.0V
Setting range: 30.0V to 32.0V
Page 39