Since conditions of use of the product are outside of the care, custody and control of R. STAHL, INC., the purchaser should determine the suitability of the product for his intended use, and assumes all risk and liability whatsoever in connection therewith.
While punching please make sure that the surfaces remain even. When determining the position of the through holes, please consider the correct clearances. Choose the applicable through-hole diameter. Ensure gaskets are not damaged. 212728 / 815060300180 Terminal Boxes for I.S. Circuits 2011-11-18·IO00·III·en·01 8150/2...
The enclosures make it necessary for the metal cable glands or conduit hubs to be bonded to the ground system. This can be accomplished by installing them either by one of the following methods. Terminal Boxes for I.S. Circuits 212728 / 815060300180 8150/2 2011-11-18·IO00·III·en·01...
Page 5
After the entry hardware is installed, connect the appropriate conduit or cable. All unused enclosure openings must be closed using approved close-up plugs with standard locknuts. (see section 11.2) 212728 / 815060300180 Terminal Boxes for I.S. Circuits 2011-11-18·IO00·III·en·01 8150/2...
The cover, gasket and mating surface is clear of debris. The cover is oriented correctly. Place the cover on the enclosure and then tighten all screws to 40 lb-in (4.5 Nm) torque. Terminal Boxes for I.S. Circuits 212728 / 815060300180 8150/2 2011-11-18·IO00·III·en·01...
Use only the following accessories in order to maintain the environmental ratings. 11.1 Conduit hub with „Increased Safety“ ground terminal Size Ordering Code 1/2″ 8166/11-01-NE 3/4″ 8166/11-02-NE 1″ 8166/11-03-NE 1-1/4″ 8166/11-04-NE 14795E00 1-1/2″ 8166/11-05-NE 2″ 8166/11-06-NE 212728 / 815060300180 Terminal Boxes for I.S. Circuits 2011-11-18·IO00·III·en·01 8150/2...
Ordering Code 1/2″ TMC050A 3/4″ TMC075A 1″ TMC100A 14796E00 1-1/4″ TMC125A 1-1/2″ TMC150A 2″ TMC20SA or TMC200A 12 Disposal The national and local waste disposal regulations have to be observed. Terminal Boxes for I.S. Circuits 212728 / 815060300180 8150/2 2011-11-18·IO00·III·en·01...
Page 9
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 10
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 11
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 12
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 13
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 14
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 15
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 16
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 17
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 18
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 19
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 20
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 21
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 22
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 23
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 24
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 25
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 26
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 27
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 28
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 29
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 30
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 31
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 32
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 33
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Page 34
Jumper links and ground wires can be neglected, in calculating the number of wires. These can be added whenever necessary. Mixed circuits of different wire sizes and current values are possible by applying the table values proportionally. Please refer to section 9.3.1 of 8150/1 Installation, Operating & Maintenance Sheet for more information. R. STAHL INC.
Need help?
Do you have a question about the 8150/ and is the answer not in the manual?
Questions and answers