Mounting

5.1

Preparations

The HCS3200 device can be mounted either on a wall or in a steel frame.
NOTICE
The temperature of the cooling fins can reach 80 °C
When mounting the device on a wall, ensure that the wall is designed to withstand
temperatures up to around 80 °C.
Minimum clearances
Maintain the following minimum clearances from other devices:
Figure 5-1
Note
• Natural convection must be possible above and below the device. A clearance of 200 mm
must be observed.
• When two heating controllers are mounted one above the other, you must ensure that the
heat emitted from the lower device is routed past the upper device.
Remove surface protection
Remove the surface protection on the front and rear of the device before installation.
SIPLUS HCS3200
Operating Instructions, 07/2014, A5E31278506C/002
Clearances for mounting an HCS3200
5