Technical data
12.1 Technical specifications
Electromagnetic compatibility
Conductor-bound parasitic coupling BURST according
to IEC 61000-4-4
Conductor-bound parasitic coupling SURGE according
to IEC 61000-4-5
Conducted interference as high-frequency radiation
according to IEC 61000-4-6
Electrostatic discharge according to IEC 61000-4-2
Field-bound parasitic coupling according to IEC
61000-4-3
EMC emitted interference
Overvoltage class
Ambient climatic conditions
Ambient temperature
during operating
during storage
during transport
Air pressure
during operating phase
during storage
Relative humidity
at 25 °C during operating maximum
at 50 °C during operating maximum
Installation altitude at a height over sea level maxi-
mum
64
2 kV power supply lines / 1 kV signal
lines
On supply lines: 1 kV symmetrical, 2 kV
asymmetrical, (24 V DC supply only with
external protective measure) PROFIBUS
cable asymmetrical 1 kV
10 V (0.15 ... 80 MHz)
4 kV contact discharge / 8 kV air dis-
charge
10 V/m (80 MHz ... 1000 MHz), 3 V/m
(1,4 GHz ... 2.0 GHz), 1 V/m (2.0 GHz
... 2.7 GHz)
in accordance with IEC 61000-6-4:2007 +
A1:2011
III
°C
0 ... 50
°C
-40 ... +70
°C
-40 ... +70
hPa
860 ... 1080
hPa
660 ... 1080
%
95
%
50
m
2000
Operating Instructions, 07/2014, A5E31278506C/002