2.4

Configure the DIP Switches

2.4.1 Setting the Node/ID Device Instance (DIP Switch A0 – A7)
The A Bank DIP switches on the ProtoNode RER allow users to set the Node-ID/Device Instance on the
Field RS-485.
DIP switches A0 – A7 can also be used to set the MAC Address for BACnet MS/TP and BACnet/IP.
A0 A1 A2 A3 A4 A5 A6 A7
Figure 1: A0 - A7 DIP Switches
Please refer to Appendix B.1 for the full range of addresses to set Node-ID/Device Instance.
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
2.4.2 Setting the Serial Baud Rate (DIP Switch B0 – B3)
DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate provided by the
interfaced systems.
Metasys N2 is always defaulted to 9600 baud and the B bank is disabled.
B0 B1 B2 B3
Figure 2: B0 – B3 DIP Switches

2.4.2.1 Baud Rate Dip Switch Selection

Baud
B0
9600
On
19200
Off
38400
On
57600
Off
76800
On
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com
Tel: (408) 964 4444 Fax: (408) 262-2269 Toll Free: 888-509-1970 X141 email: support@protocessor.com
B1
B2
B3
On
On
Off
Off
Off
On
On
Off
On
Off
On
On
Off
On
On
Page 5 of 25