Universal Gateway
ProtoAir
Instruction Manual
Application
5
The Universal Gateway (ProtoAir) provides monitoring, remote
setpoint, firing rate and burner on/off control to the Building
Automation System/ Energy Management System/ Building
7
Management System (EMS). The Universal Gateway ProtoAir
is compatible with the following brands and models:
9
Burnham Commercial Models: Products using Sage Boiler
Control (SBC™)
21
Bryan Boilers Models: BFIT, Freeflex, boilers using following
24
control components: RWF40, RWF55, RM7800, LMV36,
LMV52, PD765, LMV2_3, YB110
28
Thermal Solutions Models: APEX, AMP, Evolution, Arctic
U.S. Boiler Company Models: Alpine, ASPEN, ALTA, Citadel
34
Velocity Boiler Works Models: Phantom-X, Raptor, Phantom
39
II, Phantom-XL
There are two Universal Gateway options:
44
ProtoAir: Provides BACnet MS/TP, BACnet/IP, N2, Modbus
49
TCP communications.
LonWorks ProtoNode: Provides LonWorks communication,
52
refer to "Universal Gateway LonWorks ProtoNode" Instruction
Manual.
55
Intent
This document provides the necessary information to facilitate
Gateway installation. This Instruction Manual includes practical,
79
installation and setup detailed information. The intended users
are contractors and factory support personnel.
FPA-W44-1744
ProtoAir

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProtoAir FPA-W44-1744 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for FieldServer ProtoAir FPA-W44-1744

  • Page 1 Universal Gateway ProtoAir Instruction Manual Contents Application 1. Introduction The Universal Gateway (ProtoAir) provides monitoring, remote setpoint, firing rate and burner on/off control to the Building Automation System/ Energy Management System/ Building 2. Boiler Setup Management System (EMS). The Universal Gateway ProtoAir is compatible with the following brands and models: 3.
  • Page 2 Universal Gateway Instruction Manual The following term is used throughout this manual to bring attention to special instructions: NOTICE: Indicates special instructions on installation, operation, or service which are important but not related to personal injury hazards. NOTICE: If Building Automation System input fails, some models and controls will revert to local start command, setpoint, and firing rate.
  • Page 3: Table Of Contents

    4.3.1 Navigate to the Login Page ..........................23 5 Setup Web Server Security ....................24 5.1 Login to the FieldServer ............................24 5.2 Select the Security Mode ............................. 26 5.3 HTTPS with Own Trusted TLS Certificate ......................27 5.4 HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built-in Payload Encryption ....27 6 Setup ProtoAir ........................
  • Page 4 9.2 Setting BACnet Network Number for More Than One ProtoAir on the Subnet ............44 9.3 Change Web Server Security Settings After Initial Setup ..................44 9.4 Edit the Certificate Loaded onto the FieldServer ....................46 9.5 Change FieldServer Password ..........................46 9.6 FieldServer Manager Connection Warning Message ....................
  • Page 5: Introduction

    Up to 8 devices with one ProtoAir Figure 1-1: ProtoAir Connection Diagram The ProtoAir can connect with the MSA Grid – FieldServer Manager. The FieldServer Manager allows technicians, the OEM's support team to remotely connect to the ProtoAir. The FieldServer Manager provides the following capabilities for any registered devices in the field: •...
  • Page 6: Universal Gateway Available Configurations

    Universal Gateway Instruction Manual Universal Gateway Available Configurations The ProtoAir is shipped with the below listed configurations pre-configured and loaded. There is no need to download any configuration. The user simply selects the configuration from a list or Auto-Discovers the configuration. Table 1-1: Universal Gateway Available Configurations BACnet, N2 Type...
  • Page 7: Boiler Setup

    Universal Gateway Instruction Manual BOILER SETUP Apex, Alpine, ASPEN, Phantom-X, Raptor Boilers with Panasonic Display On Apex Boilers with Panasonic GT02 display, using the boiler mounted display, set a unique “Boiler Address” for each boiler that will be connected to the network. •...
  • Page 8: Rwf40, Lmv52, Rm7800, Lmv36, Pd765, Rwf55, Lmv2_3 Or Yb110

    Universal Gateway Instruction Manual RWF40, LMV52, RM7800, LMV36, PD765, RWF55, LMV2_3 or YB110 Refer to the Boiler’s instruction manual for password and menu navigation instructions to make the following settings: Table 2-2: RWF40, LMV52, RM7800, LMV36, PD765, RWF55, LMV2_3 or YB110 Com. Settings Model Port Setting...
  • Page 9: Wiring

    Universal Gateway Instruction Manual WIRING ProtoAir Power ProtoAir Power Requirements: Table 3-1: ProtoAir Power Requirements Power Requirements Input Voltage 12-24VDC or 24VAC Current Draw 250mA @ 12VDC 125mA @ 24VAC Max Power 3 Watts Apply power to the ProtoAir as shown below. Ensure that the power supply used complies with the specifications provided.
  • Page 10: Protoair Bacnet Or Metasys N2

    Universal Gateway Instruction Manual ProtoAir BACnet or Metasys N2 Wiring the BACnet ProtoAir to the Network (RS-485 Field Protocol) • Connection from ProtoAir to BACnet MS/TP, and Metasys N2 network. • The Field Protocol can be connected to the 3-pin connector on ProtoAir as shown. •...
  • Page 11: Bias Resistors

    Universal Gateway Instruction Manual Bias Resistors Figure 3-5: ProtoAir Bias Resistor DIP Switches The default position for Bias Resistor DIP Switches is OFF. Bias Resistors usually do not need to be enabled on the ProtoAir as there is typically another device on the RS-485 bus that has them internally, but they can be enabled if the serial communication is intermittent or experiencing issues.
  • Page 12: Termination Resistor

    Universal Gateway Instruction Manual Termination Resistor Figure 3-6: ProtoAir Termination Resistor DIP Switches The default position for the Termination Resistor DIP Switches is OFF. These are also typically unnecessary to use for this application unless experiencing issues with serial communication or data integrity. If the gateway is the last device on the serial trunk, then the End-Of-Line Termination Switch should be enabled.
  • Page 13: Thermal Solutions Boiler Control (Tsbc) And Sage Boiler Control (Sbc)

    Universal Gateway Instruction Manual Thermal Solutions Boiler Control (TSBC) and Sage Boiler Control (SBC) • The Modbus communication connects to the same RJ11 port that is used by the boiler-to-boiler communication. • Connect one end of the RJ11 cable to the TSBC/SBC and cut off the other end of the cable to access the individual wires of the RJ11 cable.
  • Page 14 Universal Gateway Instruction Manual Figure 3-9: Multiple TSBC/SBC Modbus RS485 Wiring IMPORTANT NOTES for TSBC/SBC Connections: 1. Remote On/Off Modbus Command, Register 0004 is only available when using Remote Firing Rate, not when using Remote Setpoint. EMS system must provide a contact closure to RO & C on each boiler. 2.
  • Page 15: Apex, Alpine, Aspen, Phantom-X Or Raptor With Panasonic Display

    Universal Gateway Instruction Manual Apex, Alpine, ASPEN, Phantom-X or Raptor with Panasonic Display Figure 3-10: Apex, Alpine, ASPEN, Phantom-X or Raptor with Panasonic Display Modbus RS485 Wiring The Modbus communication connects to the same RJ45 port that is used by the boiler-to-boiler communication. Connect one end of the RJ45 cable to the boiler and cut off the other end of the cable to access the individual wires of the RJ45 cable.
  • Page 16: Apex & Amp/Bfit/Citadel/Phantom-Xl 400-1000L With Concert Display

    Universal Gateway Instruction Manual Apex & AMP/BFIT/Citadel/Phantom-XL 400-1000L with Concert Display Figure 3-11: Apex and AMP/BFIT/Citadel/Phantom-XL 400-1000L with Concert Modbus RS485 Wiring There are two options for wiring the ProtoAir to an Apex or AMP/BFIT/CTD/PHX 400-1000L with Concert Display. 1. Connect one end of an RJ45 cable to the boiler PCB and cut off the other end of the cable to access the individual wires of the RJ45 cable.
  • Page 17: Older Arctic Or Freeflex 1000 With Concert Display

    Universal Gateway Instruction Manual Older Arctic or FreeFlex 1000 with Concert Display Figure 3-13: Older Arctic/FreeFlex 1000 with Concert Modbus RS485 Wiring NOTICE: 1. Arctic or FreeFlex with Concert Display is able to do both Lead Lag (Sequencer) and EMS communication at the same time.
  • Page 18: Arctic, Amp, Freeflex, Bfit & Citadel With Concert Display

    Universal Gateway Instruction Manual Arctic, AMP, FreeFlex, BFIT & Citadel with Concert Display 3.10 Figure 3-14: Arctic, AMP, FreeFlex, BFIT & Citadel with Concert Modbus RS485 Wiring NOTICE: 1. Arctic/FreeFlex, AMP/BFIT 1000-4000, & Citadel 1250-1500 with Concert Displays are able to do both Lead Lag (Sequencer) and EMS communication at the same time.
  • Page 19: Rm7800 Series

    Universal Gateway Instruction Manual RM7800 Series 3.12 Figure 3-16: RM7800 Modbus RS485 Wiring NOTICE: On the RM7800 Series; connect terminal A (RS-485+) to Pin 1 (RS-485+) on the ProtoAir 3-pin Phoenix connector. • Connect terminal CB RxD / TxD- (RS-485-) to Pin 2 (RS-485-) on the ProtoAir 3-pin Phoenix connector. •...
  • Page 20: Alta, Altac, Phantom Ii, Phantom Combi Ii Control

    Universal Gateway Instruction Manual ALTA, ALTAC, Phantom II, Phantom Combi II Control 3.13 Figure 3-17: ALTA, ALTAC, Phantom II, Phantom Combi II Control Modbus RS485 Wiring The control system has a full featured ability to interface with an Energy Management System (EMS). The control system allows remote control and monitoring via RS485 Modbus or through direct wiring.
  • Page 21: Initial Connection To Protoair

    Universal Gateway Instruction Manual INITIAL CONNECTION TO PROTOAIR Record Identification Data Each ProtoAir has a unique part number located on the back of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows: Table 4-1: PROTOAIR Identification Data Model ProtoAir...
  • Page 22: Connecting To The Gateway Via Wi-Fi Access Point

    4.2.2 Navigate to the Login Page • Open a web browser and connect to the FieldServer’s default IP Address. The default IP Address of the FieldServer for Ethernet connection is 192.168.1.24, Subnet Mask is 255.255.255.0. NOTICE: If the IP Address of the ProtoAir has been changed, the IP Address can be discovered using the FS Toolbox utility.
  • Page 23: Navigate To The Login Page

    4.3.1 Navigate to the Login Page • Open a web browser and connect to the FieldServer’s default IP Address. The default IP Address of the FieldServer for Wi-Fi Access Point connection is 192.168.50.1 NOTICE: If the IP Address of the ProtoAir has been changed, the IP Address can be discovered using the FS Toolbox utility.
  • Page 24: Setup Web Server Security

    Universal Gateway Instruction Manual SETUP WEB SERVER SECURITY Login to the FieldServer The first time the FieldServer GUI is opened in a browser, the IP Address for the gateway will appear as untrusted. This will cause the following pop-up windows to appear. •...
  • Page 25 When the login screen appears, put in the Username (default is “admin”) and the Password (found on the label of the FieldServer). NOTICE: There is also a QR code in the top right corner of the FieldServer label that shows the default unique password when scanned.
  • Page 26: Select The Security Mode

    Universal Gateway Instruction Manual Select the Security Mode On the first login to the FieldServer, the following screen will appear that allows the user to select which mode the FieldServer should use. Figure 5-5: Web Security Selection Page NOTICE: Cookies are used for authentication.
  • Page 27: Https With Own Trusted Tls Certificate

    Passphrase. • Click Save. • A “Redirecting” message will appear. After a short time, the FieldServer GUI will open. HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built -in Payload Encryption • Select one of these options and click the Save button.
  • Page 28: Setup Protoair

    Then click the Profiles Configuration button to go to the Web Configurator page. Figure 6-2: ProtoAir Web Configurator configuration page NOTICE: For Web App instructions to the System View, Data Log Viewer, Event Logger and MSA Grid – FieldServer Manager Start-up Virtual Points functions, see the Guide.
  • Page 29: Select Field Protocol And Set Configuration Parameters

    Universal Gateway Instruction Manual Select Field Protocol and Set Configuration Parameters • On the Web Configurator page, the first configuration parameter is the Protocol Selector. Figure 6-3: ProtoAir Configuration Parameters • Select the field protocol by entering the appropriate number into the Protocol Selector Value. Click the Submit button.
  • Page 30: Configure Devices Connected To The Gateway

    Universal Gateway Instruction Manual Configure Devices Connected to the Gateway 6.3.1 Use Auto-Discovery Mode This configuration method works only with devices set as Auto-Discovery in Section 1.2 Universal Gateway Available Configurations. NOTICE: Initial Auto Discovery Cycle All boilers MUST be POWERED and CONNECTED to the ProtoAir before cycling power to the ProtoAir. The ProtoAir will auto discover only connected boilers.
  • Page 31 Universal Gateway Instruction Manual NOTICE: Scroll down the page if the Active profiles header is not visible. NOTICE: Once Auto Discovery is completed, click on Discovery Mode to turn discovery off. Failure to do so will result in ProtoAir needing to “discover” all the boilers upon each power cycle.
  • Page 32: Verify Device Communications

    Universal Gateway Instruction Manual • Once the Profile for the device has been selected from the drop-down list, set Node-ID for any device attached to ProtoAir. The Node-ID needs to be uniquely assigned between 1 and 255. • Document the Node-ID that is assigned. The Node-ID assigned is used for deriving the Device Instance for BACnet/IP and BACnet MS/TP.
  • Page 33: How To Start The Installation Over: Clearing Profiles

    Universal Gateway Instruction Manual 50,000 = Node_Offset Once the Node_Offset value is input, it will be applied as shown below: ■ Device 1 Instance = 50,000 + Node_ID = 50,000 + 1 = 50,001 ■ Device 2 Instance = 50,000 + Node_ID = 50,000 + 22 = 50,022 ■...
  • Page 34: Setup Energy Management System Network

    Universal Gateway Instruction Manual SETUP ENERGY MANAGEMENT SYSTEM NETWORK Navigate to the Network Settings • From the Web App landing page, click the Settings tab on the left side of the screen. Figure 7-1: ProtoAir Web Configurator Landing Page • Click the Network tab that appears to open the Network Settings page.
  • Page 35: Change The Protoair Ip Address

    Section 7.6 Wi-Fi Access Point Settings Routing Settings The Routing settings make it possible to set up the IP routing rules for the FieldServer’s internet and network connections. • Click the Add Rule button to add a new row and set a new Destination Network, Netmask and Gateway IP Address as needed.
  • Page 36: Wi-Fi Client Settings

    Connect the FieldServer to the local network or router. NOTICE: Write down new IP Settings. Failure to do so will cause lost time. NOTICE: The browser will need to be pointed to the new IP Address of the FieldServer before the settings will be accessible again.
  • Page 37: Wi-Fi Access Point Settings

    Connect the FieldServer to the local network or router. NOTICE: If the FieldServer GUI was open in a browser via the ProtoAir Wi-Fi Access Point, the local computer will need to be reconnected to the ProtoAir Wi-Fi Access Point with the new details before the FieldServer GUI will be accessible again.
  • Page 38 Universal Gateway Instruction Manual Figure 7-7: Wi-Fi Access Point Page Page 38 of 92 Part Number 106417-04...
  • Page 39: Troubleshooting

    Universal Gateway Instruction Manual TROUBLESHOOTING Lost or Incorrect IP Address • Ensure that FieldServer Toolbox is loaded onto the local PC. Otherwise, download the FieldServer- Toolbox.zip via the MSA Safety website. • Extract the executable file and complete the installation.
  • Page 40: Viewing Diagnostic Information

    Universal Gateway Instruction Manual Viewing Diagnostic Information • Type the IP Address of the FieldServer into the web browser or use the FieldServer Toolbox to connect to the FieldServer. • Click on Diagnostics and Debugging Button, then click on view, and then on connections.
  • Page 41: Led Functions

    Diagnostic Capture will accelerate diagnosis of the problem. • Access the FieldServer Diagnostics page via one of the following methods: ◦ Open the FieldServer FS-GUI page and click on Diagnostics in the Navigation panel Page 41 of 92 Part Number 106417-04...
  • Page 42 Universal Gateway Instruction Manual ◦ Open the FieldServer Toolbox software and click the diagnose icon of the desired device Figure 8-5: Diagnostic Capture Page • Go to Full Diagnostic and select the capture period. • Click the Start button under the Full Diagnostic heading to start the capture.
  • Page 43: Wi-Fi Signal Strength

    Safari Rev. 3 and higher NOTICE: Internet Explorer is no longer supported as recommended by Microsoft. NOTICE: Computer and network firewalls must be opened for Port 80 to allow FieldServer GUI to function. Page 43 of 92 Part Number 106417-04...
  • Page 44: Additional Information

    To load a new version of the firmware, follow these instructions: 1. Extract and save the new file onto the local PC. 2. Open a web browser and type the IP Address of the FieldServer in the address bar. ◦ Default IP Address is 192.168.1.24 ◦...
  • Page 45 Universal Gateway Instruction Manual Figure 9-2: ProtoAir Diagnostics Home Page • Click Security in the Navigation panel. Figure 9-3: Security Selection Page • Click the Mode desired. ◦ If HTTPS with own trusted TLS certificate is selected, follow instructions in Section 5.3 HTTPS with Own Trusted TLS Certificate •...
  • Page 46: Edit The Certificate Loaded Onto The Fieldserver

    • If a warning message appears instead of the page as shown below, follow the suggestion that appears on screen. ◦ If the FieldServer cannot reach the server, the following message will appear Page 46 of 92 Part Number 106417-04...
  • Page 47: System Status Button

    NOTICE: If changes to the network settings are done, remember to click the Save button. Then power cycle the FieldServer by clicking on the Confirm button in the window and click on the bolded “Restart” text in the yellow pop-up box that appears in the upper right corner of the screen.
  • Page 48 Figure 9-7: ProtoAir Status NOTICE: If it was selected to opt out of the FieldServer Manager, the Grid FieldServer Manager status will not appear in the System Status window. This means the status will show as green even if the gateway is not connected to the FieldServer Manager.
  • Page 49: Protoair Specifications

    The interconnecting power connector and power cable shall: ◦ Comply with local electrical code ◦ Be suited to the expected operating temperature range ◦ Meet the current and voltage rating for the FieldServer • Furthermore, the interconnecting power cable shall: ◦...
  • Page 50: Ordering Information

    Universal Gateway Instruction Manual 10.3 Ordering information Table 10-2: ProtoAir Ordering Information ProtoAir BACnet ProtoNode LonWorks Universal Gateway (Device only) PN: 29444-3 PN: 106418-01 Universal Gateway I&O PN: 106417-04 PN: 106417-05 Universal Gateway Enclosure Kit (Includes device mounted inside PN: 112736-01 PN: 112736-02 of a plastic enclosure and I&O) Universal Gateway Wiring...
  • Page 51: Physical Dimensions

    Universal Gateway Instruction Manual 10.5 Physical Dimensions Figure 10-2: ProtoAir Mechanical Details Page 51 of 92 Part Number 106417-04...
  • Page 52: Installation Details

    Universal Gateway Instruction Manual 11 INSTALLATION DETAILS 11.1 Universal Gateway Wiring Harness Kit (PN: 112316-01) This kit is intended for use with the following boilers: AMP/BFIT 1000-4000, CTD 1250 & 1500, Arctic/FreeFlex 1500-6000. • Use the DIN rail, mounting bracket, and end anchor block to mount the ProtoAir inside of the boiler next to PCB- 06.
  • Page 53: Universal Gateway Enclosure Kit (Pn: 112736-01)

    Universal Gateway Instruction Manual Figure 11-2: ProtoAir Mounting Location for Arctic/FreeFlex 1500-6000 11.2 Universal Gateway Enclosure Kit (PN: 112736-01) This kit is intended for use with all other boilers and controls not included in the Universal Gateway Kit with Wiring Harness. •...
  • Page 54 Universal Gateway Instruction Manual Figure 11-3: ProtoAir Kit with Plastic Enclosure Page 54 of 92 Part Number 106417-04...
  • Page 55: Bacnet And Metasys N2 Points List

    Universal Gateway Instruction Manual 12 BACNET AND METASYS N2 POINTS LIST 12.1 Thermal Solutions Boiler Control (TSBC) & Sage Boiler Control (SBC) Table 12-1: TSBC/SBC BACnet and Metasys N2 Points List BACnet Read/ Modbus coil = 0 coil = 1 Notes Point Name Write Register...
  • Page 56 Universal Gateway Instruction Manual BACnet Read/ Modbus coil = 0 coil = 1 Notes Point Name Write Register Data Object Data Type Type Addr Annunciator FSG Lockout 00039 Annunciator Outlet Temp Fail 00040 Annunciator Inlet Temp Fail 00041 Annunciator OA Temp Fail 00042 Annunciator Remote Temp Fail 00043...
  • Page 57: Older Apex, Alpine/Phantom-X And Aspen/Raptor (4109 Profile)

    Universal Gateway Instruction Manual 12.2 Older Apex, Alpine/Phantom-X and ASPEN/Raptor (4109 profile) Table 12-2: Older Apex, Alpine/Phantom-X and ASPEN/Raptor BACnet and Metasys N2 Points List BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr Burner On Off (See Note 1) Enable / disable burner.
  • Page 58 Universal Gateway Instruction Manual BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr -40 F (-40°C) to 266 F (130°C) Active LL Setpoint 410,018 Setpoint determined by LL setpoint source (register 162). Supply Sensor -40 F (-40°C) to 266 F (130°C) 410,007 Return Sensor 410,011...
  • Page 59 Universal Gateway Instruction Manual BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr Fan speed not proved 24VAC voltage low/high Hardware Fault Ignition Failure Burner Cycle Count 400,128- 0-999,999 (U32) 400,129 400,130- Burner Run Time Hours (U32) 400,131 System Pum Cycle Count...
  • Page 60: Apex, Amp/Bfit/Citadel/Phantom-Xl, Alpine/Phantom-X, Arctic/Freeflex, Sola (4716 Profile)

    Universal Gateway Instruction Manual 12.3 APEX, AMP/BFIT/Citadel/Phantom-XL, Alpine/Phantom-X, Arctic/Freeflex, Sola (4716 Profile) Table 12-3: APEX, AMP/BFIT/Citadel/Phantom-XL, Alpine/Phantom-X, Arctic/Freeflex, Sola BACnet and Metasys N2 Points List BACnet Modbus Read/ Point Name Description Data Data Data Write Register Type Type Addr Enable / disable burner. Burner On Off 400,203 1 = on, 0 = off...
  • Page 61 Universal Gateway Instruction Manual BACnet Modbus Read/ Point Name Description Data Data Data Write Register Type Type Addr mA value for S2 (J8-6) parameter 4-20 mA Rem Control Input selectable as (remote set point) & (remote 400,015 modulation) Speed of the combustion air blower in rpm Fan Speed Demanded 400,009 0.01V or 0.01μA precision (0.00-50.00V)
  • Page 62 Universal Gateway Instruction Manual BACnet Modbus Read/ Point Name Description Data Data Data Write Register Type Type Addr 400,130- Burner Run Time Hours (U32) 400,131 400,132- System Pum Cycle Count 0-999,999 (U32) 400,133 400,134- DHW Pump Cycle Count 0-999,999 (U32) 400,135 400,138- Boiler Pump Cycle Count...
  • Page 63 Universal Gateway Instruction Manual BACnet Modbus Read/ Point Name Description Data Data Data Write Register Type Type Addr within the “Modbus Command timeout” seconds the following inputs are considered invalid: CH Modbus Stat, CH Modbus Setpoint, CH Sequencer Modbus Setpoint CH Modbus Rate range 30 –...
  • Page 64: Siemens Rwf40

    Universal Gateway Instruction Manual Status Description On from Lead Lag Central Heat service On from local DHW service On from Lead Lag DHW service On from local Mix service On from Lead Lag Mix service On from Lead Lag auxiliary pump X On from Lead Lag auxiliary pump Y On from Lead Lag auxiliary pump Z On, but inhibited by pump start delay...
  • Page 65: Honeywell Rm7800

    Universal Gateway Instruction Manual BACnet BACnet Point Name Data Object Data Point Type Type Address Analog Input InP3 Actual Setpoint Setpoint 1 Setpoint 2 Analog Input InP3 Actual Angular Positioning Burner Alarm Activation Remote Operation Controller Off In Remote Setpoint Switch-On Threshold Remote Switch-Off Threshold Down Remote Switch-Off Threshold Up Remote...
  • Page 66: Siemens Lmv52

    Universal Gateway Instruction Manual BACnet BACnet Point Name Data Object Data Point Type Type Address Postpurge Pre-Ignition Valve Proving Alarm Hold Lockout First Out Code * Main Valve Proof of Closure * Burner Switch * Operating Control * Auxiliary Limit 1 * Auxiliary Limit 2 * Low Water Cutoff * High Limit *...
  • Page 67 Universal Gateway Instruction Manual BACnet BACnet Point Name Data Object Data Point Type Type Address Flue Gas Combustion Efficiency Control Mode Operating Mode External Setpoint Fuel Rate Process Setpoint Hours Current Lockout Error code Current Lockout Error diagnosis Current Lockout Error class Current Lockout Error phase Current Lockout Fuel Current Lockout Output...
  • Page 68: Siemens Lmv36

    Universal Gateway Instruction Manual 12.8 Siemens LMV36 Table 12-9: Siemens LMV36 BACnet and Metasys N2 Points List BACnet BACnet Point Name Data Object Data Point Type Type Address Com Status Flame Signal Lockout Error Code Lockout Diagnostic Code Control Mode Operating Mode Fuel Rate Fuel Selected...
  • Page 69: Precision Digital Trident Pd765

    Universal Gateway Instruction Manual 12.9 Precision Digital Trident PD765 Table 12-10: Precision Digital Trident PD765 BACnet and Metasys N2 Points List BACnet BACnet N2 Data Point Name Data Object Point Type Type Address Com Status Display Value Relay 1 Status Relay 2 Status Alarm 1 Status Alarm 2 Status...
  • Page 70: Siemens Lmv2_3

    Universal Gateway Instruction Manual 12.10 Siemens LMV2_3 Table 12-11: Siemens LMV2_3 BACnet and Metasys N2 Points List BACnet BACnet N2 Data Point Name Data Object Point Type Type Address Com Status Burner control phase Pos of current fuel actuator Pos of air actuator Manipulated variable VSD Current type of fuel Current output...
  • Page 71 Universal Gateway Instruction Manual BACnet BACnet N2 Data Point Name Data Object Point Type Type Address Max output fuel 1 Operation mode of burner fuel 0 Operation mode of burner fuel 1 Error History Current Error Error History Diagnostic Code Error History Error Class Error History Error Phase Error History Type of Fuel...
  • Page 72: Fireye Yb110

    Universal Gateway Instruction Manual BACnet BACnet N2 Data Point Name Data Object Point Type Type Address Outputs Word 12 Fuel Valve 1 Fuel Valve 2 Fuel Valve 3/PV 12.11 Fireye YB110 Table 12-12: Fireye YB110 BACnet and Metasys N2 Points List BACnet BACnet N2 Data...
  • Page 73 Universal Gateway Instruction Manual BACnet BACnet N2 Data Point Name Data Object Point Type Type Address Gstat Timer Flame Logstat Sysmins Bnrmins Cycles Lockout_Count Lockout1_Msg Lockout1_Module Lockout1_BnrHrs Lockout1_BnrCycs Lockout2_Msg Lockout2_Module Lockout2_BnrHrs Lockout2_BnrCycs Lockout3_Msg Lockout3_Module Lockout3_BnrHrs Lockout3_BnrCycs Lockout4_Msg Lockout4_Module Lockout4_BnrHrs Lockout4_BnrCycs Lockout5_Msg Lockout5_Module Lockout5_BnrHrs...
  • Page 74 Universal Gateway Instruction Manual BACnet BACnet N2 Data Point Name Data Object Point Type Type Address Lockout9_Msg Lockout9_Module Lockout9_BnrHrs Lockout9_BnrCycs Lockout10_Msg Lockout10_Module Lockout10_BnrHrs Lockout10_BnrCycs Op_Control Aux_1 Aux_2 Aux_3 High_water Low_Water High_Oil_Temp Low_Oil_Temp Low_Oil_Press Low_Atom_Media Low_Gas_Press High_Gas_Press Aux_Gas High_Press High_Temp Aux_4 Aux_5 Aux_6 Aux_7...
  • Page 75: Alta/Phantom Ii Control

    Universal Gateway Instruction Manual 12.12 Alta/Phantom II Control Table 12-13: Alta/Phantom II Control BACnet and Metasys N2 Points List BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr Central Heat Enable/Disable 0 = Disable 1 = Enable This register enables single Central Heat boiler Central Heat 1 demand...
  • Page 76 Universal Gateway Instruction Manual BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr Note: When "EMS Time Out Enable*" is enabled, setpoint switches to local mode if the EMS fails to write value every 30 seconds. When disabled EMS only needs to write a valid number after power up.
  • Page 77 Universal Gateway Instruction Manual BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr This register is used when firing rate control is performed by an external building automation system. Range 0-100 % Note: When "EMS Time Out Enable*"...
  • Page 78 Universal Gateway Instruction Manual BACnet Read/ Modbus Point Name Description Data Data Data Write Register Type Type Addr Pump C (DHW Pump) 400108 Status 0 = Off, 1 = On Recirculation -40°F (-40°C) to 320°F 400038 Temperature (160°C) Table 12-14: Alta/Phantom II Lockout / Hold List Code Description Anti short cycle...
  • Page 79: Appendix A. Grid Fieldserver Manager Setup

    Appendix A. Appendix A.1. Choose Whether to Integrate the FieldServer Manager When first logging onto the ProtoAir, the Web App will open on the FieldServer Manager page. NOTICE: If a warning message appears instead, go to Section 9.6 FieldServer Manager Connection Warning Message to resolve the connection issue.
  • Page 80: Appendix A.2. User Setup

    ◦ For FieldServer Manager setup, continue with instructions in the following sections ◦ To opt out of the FieldServer Manager, click on a tab other than the Grid FieldServer Manger tab, click the checkbox next to “Opt out of Grid FieldServer Manager Registration” in the Warning window that appears and click the Exit Registration button ◦...
  • Page 81 Universal Gateway Instruction Manual Figure Appendix A-3: Grid Welcome Page NOTICE: If email received, check spam/junk folder email from notification@fieldpop.io. Contact the manufacturer’s support team if no email is found. • Click the “Complete Registration” button and fill in user details accordingly. Page 81 of 92 Part Number 106417-04...
  • Page 82: Appendix A.3. Registration Process

    • Record the email account used and password for future use. Appendix A.3. Registration Process Once the FieldServer Manager user credentials have been generated, the ProtoAir can be registered onto the server. • Click the FieldServer Manager tab. NOTICE: If a warning message appears instead, go to Section 9.6 FieldServer Manager...
  • Page 83 Click Get Started to view the FieldServer Manager registration page. • To register, fill in the user details, site details, gateway details and FieldServer Manager account credentials. ◦ Enter user details and click Next Figure Appendix A-6: Grid Account Setup Page ◦...
  • Page 84 Universal Gateway Instruction Manual Figure Appendix A-7: Grid Site Setup Page 84 of 92 Part Number 106417-04...
  • Page 85 ◦ Enter Name and Description (required) then click Next Figure Appendix A-8: Grid FieldServer Details Page ◦ Click the “Create an Grid FieldServer Manager account” button and enter a valid email to send a “Welcome to MSA Grid – FieldServer Manager” invite to the email address entered...
  • Page 86: Appendix A.4. Login To The Fieldserver Manager

    ProtoAir. Figure Appendix A-10: Grid Registration Summary NOTICE: Update these details at any time by going to the FieldServer Manager tab and clicking the Update FieldServer Details button. Appendix A.4.
  • Page 87 Universal Gateway Instruction Manual Figure Appendix A-11: Grid Sign In Page NOTICE: If the login password is lost, see the MSA Grid - FieldServer Manager Start-up Guide recovery instructions. NOTICE: For additional FieldServer Manager instructions see the MSA Grid - FieldServer Manager Start-up Guide.
  • Page 88: Appendix A.5. Change User Management Settings

    Figure Appendix A-13: Grid User Management Page User Types: Admin – Can modify and view any settings on the FieldServer. Operator – Can modify and view any data in the FieldServer array(s). Viewer – Can only view settings/readings on the FieldServer.
  • Page 89: Appendix A.7. Edit Users

    Universal Gateway Instruction Manual Figure Appendix A-14: Grid User Setup Page • Enter the new User fields: Name, Security Group and Password. ◦ User details are hashed and salted NOTICE: The password must meet the minimum complexity requirements. An algorithm automatically checks the password entered and notes the level of strength on the top right of the Password text field.
  • Page 90: Appendix A.8. Delete Users

    Universal Gateway Instruction Manual Figure Appendix A-15: Grid User Summary Page • Once the User Edit window opens, change the User Security Group and Password as needed. Figure Appendix A-16: Grid User Setup Page • Click Confirm. • Once the Success message appears, click OK. Appendix A.8.
  • Page 91 Universal Gateway Instruction Manual Figure Appendix A-17: Grid User Deletion Page • When the warning message appears, click Confirm. Figure Appendix A-18: Grid User Deletion Warning Page Page 91 of 92 Part Number 106417-04...
  • Page 92 Universal Gateway Instruction Manual Seller Limited Warranty Seller warrants its products to be free from defects in workmanship or material under normal use and service workmanship for a period of 12 months after the date of start-up or 18 months after the date of shipment, whichever shall be less.