Pyronix PCX 46 Engineer Reference Manual page 11

Hide thumbs Also See for PCX 46:
Table of Contents

Advertisement

29
Interior
32
Flood
39
CCTV
40
Perimeter
41
Patrol /
Keybox
42
Medical
43
Entry Delay 2
#These inputs cannot be bypassed.
*Use of inputs 19, 20 and 23 will make the system unable to comply with EN50131-1 Security Grade 2
or 3.
$
Ensure that these inputs are used on an entry/exit route
Choose Input
Choose an input to program.
Input In Area
Enter the areas you would like the input to operate in.
Common Input
In certain situations, a 'common' area may be needed. A common area is an area that only arms if
other specific areas are armed.
Example: A reception in a building will only need to be armed if the offices and warehouse are armed.
If the office is armed, but the warehouse isn't, then the reception would still need to be inactive so
people would be able to leave the premises. One input can be allocated to one or more areas. In this
example the inputs located in the reception area will be in the offices and warehouse areas and have
the common attribute activated.
Area A: Office - Inputs 1, 2, 3, 4 and 8. Area B: Warehouse - Inputs 5, 6, 7 and 8.
Input 8: The detector connected to this input is going to be the input located in the Reception and is
common to Area A and Area B. Input 8 will only be active if the Area A and Area B are both armed. If
one of them is disarmed the input 8 will not be active too.
5.4.1 Input Attributes?
No
Attribute
1
Chime
2
Allow
Bypass*
PCX 46 Programming Reference
This will work the same as an instant type input, the only difference is that
when CID reporting is programmed then any inputs that are programmed
as Interior will report CID event 132.
This input type will work as a 24hr input, any inputs that are programmed
for Flood will activate the external siren and will report CID event 113.
Active at all times: No audible alarm or communicator response.
The CCTV input should be connected to an external detector located next
to a CCTV camera. An output can be programmed to follow this input and
the output should be connected to a CCTV recording, transmission or other
device. An input programmed as "Line Fault" (input type 22) should also
be connected to an output of the CCTV transmission Device. If the CCTV
transmission line has been cut or missing the 'Line Fault' input will
activate. Following to this at each activation of the CCTV input the panel
will signal CID events for 'Silent Burglary' and Line Fault. No audible alarm
will be created. If the Line Fault is not active it will just log the activations
of the CCTV input into the event log.
This will work the same as an instant type input, the only difference is that
when Contact ID reporting is programmed then any inputs that are
programmed as Perimeter will report Contact ID event 131.
This input type will work similar to a switcher input, it does not trigger an
alarm but will report Contact ID event 250 and is also a useful input type
when an output is required to follow the Keybox type input.
This is a 24 Hrs type input it will activate the external sounder and report
a Contact ID event 100.
$
Any input programmed as Entry Delay 2 will act as input type 07, but the
associated entry timer will use Entry Timer 2, rather than Entry Timer 1.
Operation for both wired and wireless inputs
When enabled the system loudspeaker(s) will 'chime' when an input is
triggered whilst the alarm panel is disarmed. Chime can be single –
sounding once of follow – sounding while the door is left open. NOTE: The
chime can be turned On or Off in disarmed mode by pressing [c] when all
Entry Delay inputs are closed.
Enables the input to be manually bypassed during the arming procedure or
from the user menu whilst the panel is disarmed.
Page: 11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Enforcer 32-we

Table of Contents